Sentry Switched DC PDU
24 of 211
Terminal Block Tightening Torques
Per the manufacturer’s data sheet specifications, use the following tightening torques for the terminal block
on the 48DCWC-10-2X600-E0 unit.
Terminal Block Tightening Torques
If the terminal stud size is …
the recommended tightening torque is …
3/8” - 16
192 in.-lb. (or 16 ft.-lbs.)
¼” - 20
50 in. -lbs.
IMPORTANT: Input Terminal Requirements
For 600A operation, connections to all input terminal block poles with properly sized cable and double hole
terminal lugs are required. Otherwise, serious damage to the PDU and/or terminal block may occur.