Electrical Requirements
Part No. 70476501ENR7
57
NOTE: Minimum wire sizes are obtained from
Canadian Electrical Code and are intended for use
as a guideline only. Electrical connections should
be made only by a qualified electrical contractor in
accordance with all applicable local and national
requirements.
NOTE: Electrical specifications below are subject to
change without notice. Always refer to product serial
plate for most current specifications of product being
installed.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
NOTE: 3 Phase Only – Each tumble dryer must be
connected to its own individual branch circuit breaker,
not fuses, to avoid the possibility of “single phasing”
and causing premature failure of the motor(s).
Serial Plate Rating
Terminal Block
Connections
Required
Rated Current*
(amps)
Breaker Rating
Recommended Wire
Size AWG (mm²)
200-208/240V/60Hz/3ph L1,L2,L3 and ground
7.7
15A - 3 pole
14 (2.5)
230V/50Hz/3ph
L1,L2,L3 and ground
7.3
15A - 3 pole
14 (2.5)
380V/50 or 60Hz/3ph
L1,L2,L3 and ground
4.1
10A - 3 pole
14 (2.5)
400-415V/50Hz/3ph
L1,L2,L3 and ground
3.8
10A - 3 pole
14 (2.5)
440V/60Hz/3ph
L1,L2,L3 and ground
3.8
10A - 3 pole
14 (2.5)
460-480V/60Hz/3ph
L1,L2,L3 and ground
3.9
10A - 3 pole
14 (2.5)
* Current ratings vary slightly depending on model; refer to serial plate.
Table 7 For 120 Series Gas and Steam Tumble Dryer Models
Serial Plate Rating
Terminal Block
Connections
Required
Rated Current*
(amps)
Breaker Rating
Recommended Wire
Size AWG (mm²)
240V/60Hz/3ph
L1,L2,L3 and ground
152
175A - 3 pole
3/0 (95)
380V/50 or 60Hz/3ph
L1,L2,L3 and ground
94.5
125A - 3 pole
1 (35)
400-415V/50Hz/3ph
L1,L2,L3 and ground
87
125A - 3 pole
1 (35)
480V/60Hz/3ph
L1,L2,L3 and ground
76.1
100A - 3 pole
3 (26.2)