Rev. 4.00 December 2014
Software version 1.04
Part 1 • Page 14-10
Menu selection
Part 1 – Operating Instructions
EcoRO Dia I/II (HT)
Part 1 • Chap
ter 14
14.12 Hot RO, menu item 12
The operating parameters for hot cleaning of the reverse osmosis
system (Hot RO) can be viewed or changed in menu 12.
12 Hot RO
A) Display
B) Entry
<<
Enter
NOTICE
Hot cleaning of the reverse osmosis system can only be carried out if the following criteria
are also met:
1 EcoRO Dia I/II (HT) in standby (No dialysis mode!)
2 Aquaboss Hot Rinse installation enabled
3 Release of HotRO through automatic or manual mode (at HotRinse installation)
NOTICE
For technical reasons, the maximum temperature of the reverse osmosis system during hot
sanitation cannot exceed the hot cleaning (hot rinse) temperature.
Representation of sub-menu 12:
HotRO I:
Hot cleaning of single stage osmosis
HotRO I+II:
Hot cleaning of the 1st and 2nd osmosis stage
(at EcoRO Dia II HT)
Manual mode:
Selection of hot cleaning outside the automatic
programs available
Automatic mode:
Weekly hot cleaning program
Heating cycles RO: Successfully completed hot cycles are registered
by a counter
HotRO I + II:
Hot cleaning of the whole reverse osmosis (1st and 2nd osmosis stage)
is defined through target temperatures during heating and cool-down.
Value range:
Heating: 50…85°C / 122…185°F
Cool-down: 35…40°C / 95…104°F
HotRO I+II
Manual mode
Autom. operation
Heating cycles RO
<<
Enter
HotRO I
HotRO I+II
Manual mode
Autom. operation
Heating cycles RO
<<
Enter
HotRO I
Manual mode
Autom. operation
Heating cycles RO
<<
Enter
HotRO I+II
Heating: XXX°F
Cool down: XXX°F
<<
+ -
OK