74 / 123
Proline heating thermostat
7.13
Control parameters
The control parameters are optimized ex-works for operation as a bath thermostat (with water as the heat transfer liq-
uid) with internal control. The parameters are also preset for the operation of external containers with external control.
Sometimes however, the operation of external containers requires adaptation. In addition, the thermal capacity and vis-
cosity of the heat transfer liquid sometimes require adaptation.
The intelligent menu guidance with the Master and Command detects whether you have set the
device (as described in Section 7.7.4), to internal or external control and only displays the rele-
vant dialog boxes in each case.
Your Proline Thermostat automatically optimizes some control parameters. This automatic mech-
anism should only be deactivated and manually optimized in exceptional cases.
7.13.1
Internal control variable (integral measurement probe)
Only read further here, if you have no external temperature probe connected (and activated according to Section
7.7.4 as control variable).
Master
P1d..
3x
to
MNEnu
1x
to
P1d..
As shown in the menu structure (
7.6), the parameters for the internal
control variable can be set.
Select the parameter with or and confirm with . The set value is
displayed. Adapt it with or and confirm with .
Example: Proportional range is 8.0 K.
Proportional range
_P
= Xp
in Kelvin.
Reset time
tn
= Tn
in seconds.
Derivative time (Auto/Man)
tv
= Tv
in seconds.
The thermostat logic system only permits values with Tn > Tv!
Damping time (Auto/Man)
td
= Td
in seconds.
Tv, Td changeover to auto/ man
tvd
A
=Auto or
MN
= Manual.
The works setting is Automatic. Only experienced control technicians should
change these two parameters!
_P (0
°C
tud A
°C
Содержание PROLINE P 5 C
Страница 13: ...02 2022 Proline heating thermostat 13 123 Clear view thermostat PVL 24 Bridge thermostat PB C ...
Страница 113: ...02 2022 Proline heating thermostat 113 123 Pump characteristics measured with water ...
Страница 114: ...114 123 Proline heating thermostat 02 2022 Pump characteristics measured with water ...
Страница 115: ...02 2022 Proline heating thermostat 115 123 12 Declaration of Conformity ...
Страница 118: ......
Страница 119: ......