 g.13 - Curve parallel offset

Press the 

mode

 button (detail 10 - fi g.1) again to exit parallel curve adjustment 

mode.

If the room temperature is lower than the required value, it is advisable to set a 
higherorder curve and vice versa. Proceed by increasing or decreasing in steps of 
one andcheck the result in the room.

 

fi

 g.14 – Compensation curves

  

fi

 g.15 - Example of compensation parallel curve offset

Adjustments from Remote Timer Control

If the Remote Timer Control (optional) is connected to the boiler, the 
above adjustments are managed according to that given in table1. 

Also, the control pan-el display (detail 5 - fi g.1) shows the actual room 
temperature detected by theRemote Timer Control.

Table. 1

Heating tempera-
ture setting

Adjustment can be made from the Remote Timer Control 
menu and the boiler control panel.

DHW temperature 
adjustment 

Adjustment can be made from the Remote Timer Control 
menu and the boiler control panel.

Summer/Winter 
Switchover

Summer mode has priority over a possible Remote Timer 
Control heating demand.

Eco/Comfort 
selection

On disabling DHW from the Remote Timer Control menu, 
the boiler selects the Economy mode. In this condition, the 
button 7 - fi g.1 on the boiler panel is disabled

On enabling DHW from the Remote Timer Control menu, 
the boiler selects the Comfort mode. In this condition it is 
possible select one of the two modes with the button 7 - 
fi g.1 on the boiler panel.

Sliding Tempe-
rature

Both the Remote Timer Control and the boiler card mana-
ge Sliding Temperature adjustment: of the two, the Sliding 
Temperature of the boiler card has priority.

Water system pressure adjustment

The fi lling pressure with system cold, read on the display, must be approx. 1.0 bar. 
If thesystem pressure falls to values below minimum, the boiler card will activate 
fault F37(fi g.16). 

  

fi

 g.16 - Low system pressure fault

Once the system pressure is restored, the boiler will activate the 120-se-
condair venting cycle indicated on the display by FH.

  3.  INSTALLATION OF THE APPLIANCE

 3.1 General Instructions

BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PER-
SONNEL, IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS 
TECHNICALMANUAL, THE PROVISIONS OF CURRENT LAW, THE PRESCRIP-
TIONS OF NATIONAL AND LOCAL STANDARDS AND THE RULES OF PROPER 
WORKMANSHIP.

 3.2 Place of installation

The boiler unit must be installed in a specifi c room with ventilation openings to the 
out-side as prescribed by current regulations. If there are several burners or suction 
unitsthat can work together in the same room, the ventilation openings must be si-
zed for simultaneous operation of all the units. The place of installation must be free 
of fl ammablematerials or objects, corrosive gases, powders or volatile substances 
that, conveyed bythe burner fan, can obstruct the internal lines of the burner or the 
combustion head. Theroom must be dry and not exposed to rain, snow or frost.

If the unit is enclosed in a cabinet or mounted alongside, a space must 
be provided for removing the casing and for normal maintenance opera-
tions.

 3.3 Plumbing connections

The heating capacity of the unit must be previously established by calculating the 
building’s heat requirement according to the current regulations. The system must 
be provided with all the components for correct and regular operation.

It is advisable to installshutoff valves between the boiler and heating system allowing 
the boiler to be isolatedfrom the system if necessary.

The safety valve outlet must be connected to a funnel or collection pipe 
to prevent water spurting onto the fl oor in case of overpressure in the 
heating circuit.Otherwise, if the discharge valve cuts in and fl oods  the 
room, the boiler manufacturer cannot be held liable.

Do not use the water system pipes to earth electrical appliances.

Antes de instalar la caldera, lavar cuidadosamente todos los tubos de la instalación 
para eliminar los residuos o impurezas, que pueden comprometer el funcionamien-
to correcto del aparato.

Efectuar las conexiones a los correspondientes empalmes de acuerdo con el (capi-
tulo 5.1) y los símbolos presentes en el aparato.

High ef

fi

 ciency circulating pump

Circulating pump adjustment with boiler connected to an external hot water 
storage tank

For proper operation of the boiler KYRA D 30 UNIT COND with it connected to an 
externalhot water storage tank, the speed selector (see fi g.17) must be set to po-
sition III.

fi

 g.17 - Boiler without electrical power

Содержание KYRA D 30 UNIT COND

Страница 1: ...UCCIONES USO INSTALACI N Y MANTENIMIENTO ISTRUZIONE PER L USO L INSTALLAZIONE E LAMANUTENZIONE INSTRUCTIONS FOR USE INSTALLATIONAND MAINTENANCE ES IT EN KYRA D 30 UNIT COND 1E3010302 Cod A73022680 201...

Страница 2: ...5 Conexiones el ctricas 7 3 6 Conexi n a la chimenea 7 3 7 Conexi n de la descarga de condensados 7 4 SERVICIO Y MANTENIMIENTO 7 4 1 Regulaciones 7 4 2 Puesta en servicio 8 4 3 Mantenimiento 9 4 4 So...

Страница 3: ...este caso el control debe ser confi gurado como se indica en la pag 4 KYRA D 30 UNIT COND es un generador t rmico para calefacci n con condensa ci n de alto rendimiento y bajo nivel de emisiones El c...

Страница 4: ...sanitaria Configuraci n Opcional Mediante las teclas del ACS 1 y 2 fig 1 se puede regular la temperatura desde un m nimo de 40 C hasta un m ximo de 65 C fig 11 Regulaci n de la temperatura ambiente co...

Страница 5: ...que se indica en pantalla con la expresi n FH 3 INSTALACI N DEL APARATO 3 1 Disposiciones generales LA CALDERA TIENE QUE SER INSTALADA NICAMENTE POR PERSONAL ESPECIALIZADO Y DEBIDAMENTE CUALIFICADO RE...

Страница 6: ...el intercambiador de la caldera ni ning n otro componente o material del aparato o de la instalaci n Se proh be usar l quidos anticongelantes aditivos e inhibidores gen ricos que no est n expre sament...

Страница 7: ...del equipo se debe conectar a un desag e apropiado a trav s de un sif n suministrado Respetar las normas nacionales y locales sobre la descarga de aguas de condensaci n en la red de alcantarillado Pa...

Страница 8: ...s de montar el inyector controlar la posici n de los electrodos y del deflector seg n las cotas indicadas a continuaci n Es necesario efectuar un control de las cotas despu s de cada intervenci n en e...

Страница 9: ...positivos de mando y segu ridad Comprobar la eficacia de la tuber a de salida de humos Controlar que no haya obstrucciones o abolladuras en los tubos de entrada y retorno del combustible Limpiar el fi...

Страница 10: ...03 Actuaci n de la protecci n contra sobretemperaturas Sensor de calefacci n averiado Controlar la posici n y el funcionamiento del sensor de calefacci n No circula agua en la instalaci n Controlar la...

Страница 11: ...160V Sobrecarga del motor Rojo parpadeante Circulador bloqueado por causa interna Motor bloqueado Sistema electr nico da ado 5 CARACTER STICAS Y DATOS T CNICOS 5 1 Dimensiones conexiones y componentes...

Страница 12: ...e autom tico 56 Vaso de expansi n 191 Sensor de la temperatura de humos 246 Transductor de presi n 275 Llave de descarga circuito calefacci n 278 Sensor doble seguridad calefacci n 295 Quemador 5 3 Di...

Страница 13: ...o Pm x 50 30 C 102 3 Rendimiento Pm n 50 30 C 105 5 Rendimiento 30 103 7 Clase de eficiencia seg n directiva 92 42 CE Presi n m xima funcionamiento calefacci n bar 3 PMS Presi n m nima funcionamiento...

Страница 14: ...alta temperatura 4 91 0 A 30 de potencia calor fica nominal y r gimen de baja temperatura 1 97 5 Consumo de electricidad auxiliar A plena carga elmax kW 0 188 A carga parcial elmin kW 0 075 En modo de...

Страница 15: ...nte opcional 95 V lvula de 3 v as 2 conductores con resorte de retorno no suministrada 138 Sonda exterior opcional 139 Cronomando a distancia opcional 191 Sensor de temperatura de los humos 246 Transd...

Страница 16: ...nna fumaria 21 3 7 Collegamento scarico condensa 21 Verificare periodicamente la presenza di acqua nel sifone 21 4 SERVIZIO E MANUTENZIONE 21 4 1 Regolazioni 21 4 2 Messa in servizio 22 4 3 Manutenzio...

Страница 17: ...fornisce importanti indicazioni riguardanti la sicurezza di installazione uso e manutenzione KYRA D 30 UNIT COND un generatore termico per riscaldamento premiscelatoa condensazione ad altissimo rendim...

Страница 18: ...fig 1 per variare la temperatura da un minimo di40 C ad un massimo di 65 C fig 11 Regolazione della temperatura ambiente con termostato ambiente opzionale Impostare tramite il termostato ambiente la...

Страница 19: ...VE ESSERE EFFETTUATA SOLTANTO DAPERSONALE SPECIALIZZATO E DI SICURA QUALIFICAZIONE OTTEMPE RANDO ATUTTE LE ISTRUZIONI RIPORTATE NEL PRESENTE MANUALE TEC NICO ALLE DISPOSIZIONI DI LEGGE VIGENTI ALLE PR...

Страница 20: ...suoi prodotti sono idonei all uso e non arrecano danni allo scambiatore di caldaia o ad altri componenti e o materiali di caldaia ed impianto proibito l uso di liquidiantingelo additivi e inibitori ge...

Страница 21: ...collegato ad una idonea rete di smaltimento interponendo un sifone di scarico non fornito Rispettare le normative specifiche nazionali e locali riguardanti l immissione dell acqua di condensa nella re...

Страница 22: ...g 31 Posizione elettrodi deflettore Dopo avere montato l ugello verificare il corretto posizionamento di elettrodi e defle ttore secondo le quote sotto indicate E opportuno eseguire una verifica delle...

Страница 23: ...icurezza devono funzionare correttamente Il circuito di evacuazione fumi deve essere in perfetta efficienza Controllare che non ci siano eventuali occlusioni o ammaccature nei tubi di ali mentazione e...

Страница 24: ...protezione sovra temperatura Sensore riscaldamento danneggiato Controllare il corretto posizionamento e funzio namento del sensore di riscaldamento Mancanza di circolazione d acqua nell impianto Veri...

Страница 25: ...ufficente 160V Sovracarico motore Rosso Lampeggiante Circolatore bloccato per causa interna Motore bloccato Elettronica danneggiata 5 CARATTERISTICHE E DATI TECNICI 5 1 Dimensioni attacchi e component...

Страница 26: ...Vaso di espansione 191 Sensore di temperatura fumi 246 Trasduttore di pressione 275 Rubinetto di scarico impianto di riscaldamento 278 Sensore doppio Sicurezza riscaldamento 295 Bruciatore 5 3 Perdit...

Страница 27: ...o Pm x 50 30 C 102 3 Rendimento Pm n 50 30 C 105 5 Rendimento 30 103 7 Classe efficienza direttiva 92 42 EEC Pressione max esercizio riscaldamento bar 3 PMS Pressione min esercizio riscaldamento bar 0...

Страница 28: ...Efficienza utile Alla potenza termica nominale e a un regime di alta temperatura 4 91 0 Al 30 della potenza termica nominale e a un regime di bassa temperatura 1 97 5 Consumo ausiliario di elettricit...

Страница 29: ...o 72 Termostato ambiente opzionale 95 Valvola a 3 vie 138 Sonda esterna opzionale 139 Unit ambiente opzionale 191 Sensore di temperatura fumi 246 Trasduttore di pressione 278 Sensore doppio Sicurezza...

Страница 30: ...34 3 5 Electrical connections 35 3 6 Connection to the flue 35 3 7 Condensate drain connection 35 4 SERVICE AND MAINTENANCE 35 4 1 Adjustments 35 4 2 Commissioning 36 4 3 Maintenance 37 4 4 Troublesho...

Страница 31: ...f the art technology high reliability and constructive quality Please read this manual carefully as it provides important information about installation use and maintenance KYRA D 30 UNIT COND is a th...

Страница 32: ...C fig 10 DHW temperature adjustment Use the DHW buttons details 1 and 2 fig 1 to adjust the temperature from a min of 10 C to a max of 65 C fig 11 Room temperature adjustment with optional room thermo...

Страница 33: ...RDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICALMANUAL THE PROVISIONS OF CURRENT LAW THE PRESCRIP TIONS OF NATIONAL AND LOCAL STANDARDS AND THE RULES OF PROPER WORKMANSHIP 3 2 Place of install...

Страница 34: ...amageto the heat exchanger or other components and or materials of the boiler unit and system It is prohibited to use generic antifreeze fluid additives or inhibitors that are not expressly suited for...

Страница 35: ...the joints At the points of union it is recommended to check the tightness and thermally insulate the entire duct between the boiler and chimney in order to avoid the forma tion of condensation 3 7 C...

Страница 36: ...lock the screw 3 fig 31 Position of electrodes baffle After fitting the nozzle check correct positioning of the electrodes and baffle ac cordingto the dimensions given below It is advisable to check...

Страница 37: ...rfectly efficient Check there are no obstructions or dents in the fuel supply and return pipes Clean the filter of the fuel suction line Measure the correct fuel consumption Clean the combustion head...

Страница 38: ...e short circuit Replace the photore sistance Extraneous light strikes the photoresistance Eliminate the light source A03 Overtemperature protection activation Heating sensor damaged Check the correct...

Страница 39: ...to external causes Overvoltage 270V Insufficient voltage 160V Motor overload Red Flashing Circulating pump blocked due to internal causes Motor blocked Damaged electronics 5 TECHNICAL DATA AND CHARACT...

Страница 40: ...ating pump 36 Automatic air vent 56 Expansion vessel 191 Smoke temperature sensor 246 Pressure transducer 275 Key download heating circuit 278 Double sensor Safety heating 295 Burner 5 3 Diagrams Circ...

Страница 41: ...Efficiency Pmax 50 30 C 102 3 Efficiency Pmin 50 30 C 105 5 Efficiency 30 103 7 Efficiency class according to directive 92 42 CE Max working pressure in heating bar 3 PMS Min working pressure in heati...

Страница 42: ...Useful efficiency Useful heat output at rated heat output and high temperature regime 4 91 0 Useful heat output at 30 of rated heat output and low temperature regime 1 97 5 Auxiliary electricity consu...

Страница 43: ...nal 72 Room thermostat optional 95 3 way valve 2 conductors with return spring not supplied 138 External probe optional 139 Remote Timer Control optional 191 Smoke temperature sensor 246 Pressure tran...

Страница 44: ......

Отзывы: