LAARS Heating Systems
Page 86
Label
Description
How to Reach
Lead lag on
hysteresis
When the Lead/Lag function is enabled, the
control system will not fire the boilers until the
temperature at the System sensor drops to the
Lead/Lag CH setpoint minus a hysteresis value
(normally about 10°F).
If Lead/Lag enabled –
<’home’ screen> Lead/Lag Master button
<Lead/Lag Master screen> Configure
button <Lead/Lag Master Configuration
screen>
Lead lag P
gain
This is part of the damping function
(“Proportional”) used when the controller
interprets the input from the System sensor.
<’home’ screen> Lead/Lag Master button
<Lead/Lag Master screen> Configure
button <Lead/Lag Master Configuration
screen> Advanced Settings button/ Left-
or Right- arrow buttons <Modulation
screen>
Lead/Lag
Slave Enable
Select Enable Slave for Built-in Lead/Lag
Master. Be sure this is turned on for each
controller in the system.
<’home’ screen> Select a controller
<Status Summary screen> Configure
button <Configuration Menu> Select line
for LL Slave Configuration <Lead/Lag
Slave Configuration screen>
Lead/
Lag Slave
Sequence
Order
Enter the position of this Slave in the sequence.
Be sure to enter this for each Slave in the
system.
<’home’ screen> Select a controller
<Status Summary screen> Configure
button <Configuration Menu> Select line
for LL Slave Configuration <Lead/Lag
Slave Configuration screen>
Lead/
Lag Slave
Modbus
Address
Each slave must have a unique Modbus address.
Be sure to enter this for each controller in the
system.
<’home’ screen> Select a controller
<Status Summary screen> Configure
button <Configuration Menu> Select line
for LL Slave Configuration <Lead/Lag
Slave Configuration screen>
Lead/Lag
Outdoor
Reset Enable
Enable = Outdoor Reset feature turned on
<’home’ screen> Lead/Lag Master button
<Lead/Lag Master screen> Configure
button <Lead/Lag Master Configuration
screen> Advanced Settings button/ Left-
or Right- arrow buttons <Outdoor Reset
screen>
Lead/Lag
Outdoor
Reset
low water
temperature
This parameter is used as the normal setpoint
above the point where Outdoor Reset stops
adjusting for a higher outdoor temperature (the
Max. Outdoor Temperature value)
<’home’ screen> Lead/Lag Master button
<Lead/Lag Master screen> Configure
button <Lead/Lag Master Configuration
screen> Advanced Settings button/ Left-
or Right- arrow buttons <Outdoor Reset
screen>
Lead/Lag
Outdoor
Reset max
outdoor
temperature
If Lead/Lag is enabled, this is the maximum
outdoor temperature at which the Outdoor Reset
feature will be active.
<’home’ screen> Lead/Lag Master button
<Lead/Lag Master screen> Configure
button <Lead/Lag Master Configuration
screen> Advanced Settings button/ Left-
or Right- arrow buttons <Outdoor Reset
screen>
Lead/Lag
Outdoor
Reset min
outdoor
temperature
If Lead/Lag is enabled, this is the minimum
outdoor temperature at which the Outdoor Reset
feature will be active.
<’home’ screen> Lead/Lag Master button
<Lead/Lag Master screen> Configure
button <Lead/Lag Master Configuration
screen> Advanced Settings button/ Left-
or Right- arrow buttons <Outdoor Reset
screen>
Содержание NTH1000
Страница 4: ...LAARS Heating Systems ...
Страница 11: ...NeoTherm LC Boilers and Water Heaters Page 7 Fig 6 Dimensions NT 1700 ...
Страница 37: ...NeoTherm LC Boilers and Water Heaters Page 33 Fig 21 Ladder Diagram ...
Страница 38: ...LAARS Heating Systems Page 34 Fig 22 Wiring Diagram ...
Страница 39: ...NeoTherm LC Boilers and Water Heaters Page 35 ...
Страница 51: ...NeoTherm LC Boilers and Water Heaters Page 47 Fig 51 Connection Terminals ...
Страница 128: ...LAARS Heating Systems Page 124 Fig 140 Machine Frame NT1000 13 3 Parts Illustrations ...
Страница 129: ...NeoTherm LC Boilers and Water Heaters Page 125 Fig 141 Rear Panel NT1000 Fig 142 Rear Panel NT1700 ...
Страница 130: ...LAARS Heating Systems Page 126 Fig 143 Machine Frame NT1700 ...
Страница 131: ...NeoTherm LC Boilers and Water Heaters Page 127 Fig 144 Front Panels and Covers NT1000 and NT1700 ...
Страница 132: ...LAARS Heating Systems Page 128 Fig 145 Burners and Combustion Chamber NT1000 ...
Страница 133: ...NeoTherm LC Boilers and Water Heaters Page 129 Fig 146 Burners and Combustion Chamber NT1700 ...
Страница 134: ...LAARS Heating Systems Page 130 Fig 147 Heat Exchanger Components NT1000 and NT1700 Fig 148 Burner Detail NT1000 ...
Страница 135: ...NeoTherm LC Boilers and Water Heaters Page 131 Fig 149 Burner Detail NT1700 ...
Страница 136: ...LAARS Heating Systems Page 132 Fig 150 Electronic Components Fig 151 Condensate Trap NT1000 ...
Страница 137: ...NeoTherm LC Boilers and Water Heaters Page 133 Fig 152 Condensate Trap NT1700 Fig 153 Flow Switch NT1000 and NT1700 ...
Страница 138: ...LAARS Heating Systems Page 134 This page intentionally left blank ...
Страница 139: ...NeoTherm LC Boilers and Water Heaters Page 135 This page intentionally left blank ...