NeoTherm LC Boilers and Water Heaters
Page 57
Job D - Disable the Lead/Lag Master
Function on the Lead/Lag Slaves
(This is an individual function – do this for each of the controls,
except the one used as the Lead/Lag Master. Use the separate
Touch Screen on each boiler.)
At the beginning of this section, we described
the Master and Slave arrangement used with the
Lead/Lag system. In the previous section, we
explained how to set up one controller as the Lead/
Lag Master. As we said, the controller used as the
Master (usually the Primary controller for Boiler 1)
also serves as a Slave (usually Slave 1). A single
controller performs both functions.
When the controllers arrive from the Laars factory,
they will all be configured as slaves. Your job in this
step is to disable the Lead/Lag Master function on
each of the controls, except for the one control that
will be used as the Lead/Lag Master – usually the
Primary control on Boiler 1.
1. From the ‘home’ screen (Fig. 59), press the
icon for the controller you want to work
with. In this example, we will start with the
Secondary controller for Boiler 1, and make
sure this is not set up as a Master.
Fig. 59 – ‘home’ screen
2. The system will take you to the Status
Summary screen.
Fig. 60 – Status Summary Screen
3. To disable the Master function on this
controller, press the Configure button. Figure
61 shows the Configuration screen.
Fig. 61 – Configuration Screen
4. Scroll down through the list until you find the
line for LL Master Configuration. See Fig. 62.
Fig. 62 – Lead/Lag Master Configuration
Press on the line for Master Enable. The
system will go to a separate screen and ask
you to login using a password. Enter the
password (see Section 8.2), return to the
Master Configuration screen, then press the
line for Master Enable again. Change the
entry to Disabled.
Don’t change any of the other entries on this
screen.
5. At this point, you have disabled the Master
function on one of the controllers. You will
need to repeat the process for each of the other
controllers in the system (except the Primary
Controller on Boiler 1).
Go to the Touch Screen on the next boiler.
Repeat steps 1 through 4 for the first controller
on that boiler.
6. Repeat the steps listed above for each of the
other controllers on the system. Disable the
Master function on each of them.
Содержание NTH1000
Страница 4: ...LAARS Heating Systems ...
Страница 11: ...NeoTherm LC Boilers and Water Heaters Page 7 Fig 6 Dimensions NT 1700 ...
Страница 37: ...NeoTherm LC Boilers and Water Heaters Page 33 Fig 21 Ladder Diagram ...
Страница 38: ...LAARS Heating Systems Page 34 Fig 22 Wiring Diagram ...
Страница 39: ...NeoTherm LC Boilers and Water Heaters Page 35 ...
Страница 51: ...NeoTherm LC Boilers and Water Heaters Page 47 Fig 51 Connection Terminals ...
Страница 128: ...LAARS Heating Systems Page 124 Fig 140 Machine Frame NT1000 13 3 Parts Illustrations ...
Страница 129: ...NeoTherm LC Boilers and Water Heaters Page 125 Fig 141 Rear Panel NT1000 Fig 142 Rear Panel NT1700 ...
Страница 130: ...LAARS Heating Systems Page 126 Fig 143 Machine Frame NT1700 ...
Страница 131: ...NeoTherm LC Boilers and Water Heaters Page 127 Fig 144 Front Panels and Covers NT1000 and NT1700 ...
Страница 132: ...LAARS Heating Systems Page 128 Fig 145 Burners and Combustion Chamber NT1000 ...
Страница 133: ...NeoTherm LC Boilers and Water Heaters Page 129 Fig 146 Burners and Combustion Chamber NT1700 ...
Страница 134: ...LAARS Heating Systems Page 130 Fig 147 Heat Exchanger Components NT1000 and NT1700 Fig 148 Burner Detail NT1000 ...
Страница 135: ...NeoTherm LC Boilers and Water Heaters Page 131 Fig 149 Burner Detail NT1700 ...
Страница 136: ...LAARS Heating Systems Page 132 Fig 150 Electronic Components Fig 151 Condensate Trap NT1000 ...
Страница 137: ...NeoTherm LC Boilers and Water Heaters Page 133 Fig 152 Condensate Trap NT1700 Fig 153 Flow Switch NT1000 and NT1700 ...
Страница 138: ...LAARS Heating Systems Page 134 This page intentionally left blank ...
Страница 139: ...NeoTherm LC Boilers and Water Heaters Page 135 This page intentionally left blank ...