Page 8
Section 2
LOCATING THE APPLIANCE
2.1
Locating the Appliance
The NeoTherm LC may be installed indoors or
outdoors. The unit may only be installed outdoors
in a location which will never experience freezing
temperatures. Choose a location for the unit which
allows clearances on all sides for maintenance and
inspection. See Table 1. Always install the unit on a
firm, level surface. Level the unit using the leveling
feet.
The unit should not be located in an area where
leakage of any connections will result in damage to
the area adjacent to the appliance, or to lower floors
of the structure.
When this type of location is not available, install
a suitable drain pan, adequately drained, under the
appliance.
The appliance is design-certified by CSA-
International for installation on combustible flooring;
in basements; in closets, utility rooms or alcoves
.
NeoTherm LC boilers must never be installed
on carpeting.
The location for the appliance should
be chosen with regard to the vent pipe lengths and
external plumbing.
The unit shall be installed such that the gas ignition
system components are protected from water (dripping,
spraying, rain, etc.) during operation and service
(circulator replacement, control replacement, etc.).
When vented vertically, the NeoTherm LC must be
located as close as practical to the vertical section
of the vent. If the vent terminal and/or combustion
air terminal terminate through a wall, and there is
potential for snow accumulation in the local area,
both terminals should be installed at an appropriate
level above grade or the maximum expected snow
line.
The dimensions and requirements that are shown in
Table 1 should be met when choosing the locations
for the appliance.
2.2
Correct Vent Distance from
Outside Wall or Roof Termination
The forced draft combustion air blower in the
appliance has sufficient power to vent properly when
the guidelines in Table 2
are followed.
Note -
When located on the same wall, the
NeoTherm LC combustion air intake terminal must
be installed a minimum of 12” below the exhaust
terminal. There must also be a minimum horizontal
distance from intake to the exhaust terminal of 36.”
APPLIANCE
SUGGESTED SERVICE ACCESS CLEARANCE
SURFACE
INCHES
CM
Front
24
60.9
Left Side
12
30.5
Right Side
18
45.7
Back
24
60.9
Top
24
60.9
APPLIANCE
REQUIRED CLEARANCE TO COMBUSTIBLES
SURFACE
INCHES
CM
Front
2
5.1
Left Side
0
0
Right Side
0
0
Back
0
0
Top
8
20.3
Vent
1
2.6
INTAKE / EXHAUST
STANDARD
MAX EQUIV.
SIZE VENT
FT.
M
1000 6”
100
30
1700 8”
100
30
Installations in the U.S. require exhaust vent pipe that is PVC or
CPVC complying with ANSI/ASTM D1785 F441, polypropylene
complying with ULC-S636, or stainless steel complying with
UL1738. Installations in Canada require exhaust vent pipe that is
certified to ULC S636.
Intake (air) pipe must be PVC or CPVC that complies with ANSI/
ASTM D1785 F441, ABS that complies with ANSI/ASTM D1527,
stainless steel, or galvanized material.
Closet and alcove installations do not allow the use of PVC under
any circumstances
To calculate max equivalent length, measure the linear feet of the
pipe, and add 5 feet
(1.5 m)
for each elbow used.
Table 2 - Vent / Air Pipe Sizes
Table 1 - Clearances
For the concentric vent terminal kit (optional), follow
the installation instructions included with the kit.
Содержание NTH1000
Страница 4: ...LAARS Heating Systems ...
Страница 11: ...NeoTherm LC Boilers and Water Heaters Page 7 Fig 6 Dimensions NT 1700 ...
Страница 37: ...NeoTherm LC Boilers and Water Heaters Page 33 Fig 21 Ladder Diagram ...
Страница 38: ...LAARS Heating Systems Page 34 Fig 22 Wiring Diagram ...
Страница 39: ...NeoTherm LC Boilers and Water Heaters Page 35 ...
Страница 51: ...NeoTherm LC Boilers and Water Heaters Page 47 Fig 51 Connection Terminals ...
Страница 128: ...LAARS Heating Systems Page 124 Fig 140 Machine Frame NT1000 13 3 Parts Illustrations ...
Страница 129: ...NeoTherm LC Boilers and Water Heaters Page 125 Fig 141 Rear Panel NT1000 Fig 142 Rear Panel NT1700 ...
Страница 130: ...LAARS Heating Systems Page 126 Fig 143 Machine Frame NT1700 ...
Страница 131: ...NeoTherm LC Boilers and Water Heaters Page 127 Fig 144 Front Panels and Covers NT1000 and NT1700 ...
Страница 132: ...LAARS Heating Systems Page 128 Fig 145 Burners and Combustion Chamber NT1000 ...
Страница 133: ...NeoTherm LC Boilers and Water Heaters Page 129 Fig 146 Burners and Combustion Chamber NT1700 ...
Страница 134: ...LAARS Heating Systems Page 130 Fig 147 Heat Exchanger Components NT1000 and NT1700 Fig 148 Burner Detail NT1000 ...
Страница 135: ...NeoTherm LC Boilers and Water Heaters Page 131 Fig 149 Burner Detail NT1700 ...
Страница 136: ...LAARS Heating Systems Page 132 Fig 150 Electronic Components Fig 151 Condensate Trap NT1000 ...
Страница 137: ...NeoTherm LC Boilers and Water Heaters Page 133 Fig 152 Condensate Trap NT1700 Fig 153 Flow Switch NT1000 and NT1700 ...
Страница 138: ...LAARS Heating Systems Page 134 This page intentionally left blank ...
Страница 139: ...NeoTherm LC Boilers and Water Heaters Page 135 This page intentionally left blank ...