NeoTherm LC Boilers and Water Heaters
Page 83
Label
Description
How to Reach
CH (Central
Heat)
Setpoint
This setpoint is used when the time-of-day input
is off. If the outdoor reset function is active, this
setpoint provides one coordinate for the outdoor
reset curve. See the section for the CH Outdoor
Reset parameter.
If Lead/Lag enabled –
<’home’ screen> Lead/Lag Master button
<Lead/Lag Master screen> Configure
button <Lead/Lag Master Configuration
screen>
CH (Central
Heat) “Time
of Day”
Setpoint
This setpoint is used when the time-of-day input
is on. If the outdoor reset function is active,
this Setpoint provides one coordinate for the
shifted outdoor reset curve, because the time-
of-day switch is on. See the section for the CH
Outdoor Reset parameter.”
If Lead/Lag enabled –
<’home’ screen> Lead/Lag Master button
<Lead/Lag Master screen> Configure
button <Lead/Lag Master Configuration
screen>
DHW
(Domestic
Hot Water) D
Gain
This gain applied to the Differential term of the
PID equation for the DHW loop.
<’home’ screen> Select a controller
<Status Summary screen> Configure
button <Domestic Hot Water
Configuration screen>
DHW
(Domestic
Hot Water)
Enable
This parameter determines whether the
Domestic Hot Water loop is enabled or disabled.
When it is disabled, the demand caused by the
DHW sensor is ignored. It may be disabled to
turn it off temporarily or because the application
does not use this feature.
<’home’ screen> Select a controller
<Status Summary screen> Configure
button <Domestic Hot Water
Configuration screen>
DHW
(Domestic
Hot Water)
has priority
over CH
(Central
Heat)
This parameter determines the priority of
Domestic Hot Water vs. Central Heat call-for-
heat, when both of these are enabled and active.
(The DHW priority also may shift for a period
of time, as specified by DHW Priority time and
method parameters.)”
<’home’ screen> Lead Lag Master <Lead
Lag Master screen> Configure button
<Lead Lag Master Configuration screen>
Advanced Settings button/ Left- and
Right- arrow buttons <Domestic Hot
Water screen>
DHW
(Domestic
Hot Water) I
gain
This gain applied to the Integral term of the PID
equation for the DHW loop.
<’home’ screen> Select a controller
<Status Summary screen> Configure
button <Domestic Hot Water
Configuration>
DHW
(Domestic
Hot Water)
off hysteresis
The off hysteresis is added to the Domestic Hot
Water Setpoint to determine the temperature at
which the DHW burner demand turns off.
<’home’ screen> Select a controller
<Status Summary screen> Configure
button <Domestic Hot Water
Configuration screen>
DHW
(Domestic
Hot Water)
on hysteresis
The on hysteresis is subtracted from the
Domestic Hot Water Setpoint to determine the
temperature at which the DHW burner demand
turns on.
<’home’ screen> Select a controller
<Status Summary screen> Configure
button <Domestic Hot Water
Configuration>
DHW
(Domestic
Hot Water) P
gain
This gain applied to the Proportional term of the
PID equation for the DHW loop.
<’home’ screen> Select a controller
<Status Summary screen> Configure
button <Domestic Hot Water
Configuration screen>
DHW
(Domestic
Hot Water)
priority
override time
If this parameter is non-zero then a Domestic
Hot Water demand will shift its priority vs.
other demand sources according to the specified
time. The priority override timing is reset when
demand from the DHW source turns off.
<’home’ screen> Lead Lag Master button
<Lead Lag Master screen> Configure
button <Lead Lag Master Configuration
screen> Advanced Settings button
<Domestic Hot Water screen>
Содержание NTH1000
Страница 4: ...LAARS Heating Systems ...
Страница 11: ...NeoTherm LC Boilers and Water Heaters Page 7 Fig 6 Dimensions NT 1700 ...
Страница 37: ...NeoTherm LC Boilers and Water Heaters Page 33 Fig 21 Ladder Diagram ...
Страница 38: ...LAARS Heating Systems Page 34 Fig 22 Wiring Diagram ...
Страница 39: ...NeoTherm LC Boilers and Water Heaters Page 35 ...
Страница 51: ...NeoTherm LC Boilers and Water Heaters Page 47 Fig 51 Connection Terminals ...
Страница 128: ...LAARS Heating Systems Page 124 Fig 140 Machine Frame NT1000 13 3 Parts Illustrations ...
Страница 129: ...NeoTherm LC Boilers and Water Heaters Page 125 Fig 141 Rear Panel NT1000 Fig 142 Rear Panel NT1700 ...
Страница 130: ...LAARS Heating Systems Page 126 Fig 143 Machine Frame NT1700 ...
Страница 131: ...NeoTherm LC Boilers and Water Heaters Page 127 Fig 144 Front Panels and Covers NT1000 and NT1700 ...
Страница 132: ...LAARS Heating Systems Page 128 Fig 145 Burners and Combustion Chamber NT1000 ...
Страница 133: ...NeoTherm LC Boilers and Water Heaters Page 129 Fig 146 Burners and Combustion Chamber NT1700 ...
Страница 134: ...LAARS Heating Systems Page 130 Fig 147 Heat Exchanger Components NT1000 and NT1700 Fig 148 Burner Detail NT1000 ...
Страница 135: ...NeoTherm LC Boilers and Water Heaters Page 131 Fig 149 Burner Detail NT1700 ...
Страница 136: ...LAARS Heating Systems Page 132 Fig 150 Electronic Components Fig 151 Condensate Trap NT1000 ...
Страница 137: ...NeoTherm LC Boilers and Water Heaters Page 133 Fig 152 Condensate Trap NT1700 Fig 153 Flow Switch NT1000 and NT1700 ...
Страница 138: ...LAARS Heating Systems Page 134 This page intentionally left blank ...
Страница 139: ...NeoTherm LC Boilers and Water Heaters Page 135 This page intentionally left blank ...