NeoTherm LC Boilers and Water Heaters
Page 109
Code Description
L or
H
Procedure
200
Invalid lightoff rate setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
201
Invalid lightoff rate proving setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
202
Invalid MFEP (Main Flame Establishing
Period) time setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
203
Invalid MFEP (Main Flame Establishing
Period) flame failure response setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
204
Invalid NTC sensor type setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
205
Invalid Outlet high limit response
setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
207
Invalid PII (Pre-Ignition Interlock)
enable setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
210
Invalid Postpurge time setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
211
Invalid Power up with lockout setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
212
Invalid Preignition time setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
213
Invalid Prepurge rate setting
L
1. Return to Configuration mode and recheck
selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
Содержание NTH1000
Страница 4: ...LAARS Heating Systems ...
Страница 11: ...NeoTherm LC Boilers and Water Heaters Page 7 Fig 6 Dimensions NT 1700 ...
Страница 37: ...NeoTherm LC Boilers and Water Heaters Page 33 Fig 21 Ladder Diagram ...
Страница 38: ...LAARS Heating Systems Page 34 Fig 22 Wiring Diagram ...
Страница 39: ...NeoTherm LC Boilers and Water Heaters Page 35 ...
Страница 51: ...NeoTherm LC Boilers and Water Heaters Page 47 Fig 51 Connection Terminals ...
Страница 128: ...LAARS Heating Systems Page 124 Fig 140 Machine Frame NT1000 13 3 Parts Illustrations ...
Страница 129: ...NeoTherm LC Boilers and Water Heaters Page 125 Fig 141 Rear Panel NT1000 Fig 142 Rear Panel NT1700 ...
Страница 130: ...LAARS Heating Systems Page 126 Fig 143 Machine Frame NT1700 ...
Страница 131: ...NeoTherm LC Boilers and Water Heaters Page 127 Fig 144 Front Panels and Covers NT1000 and NT1700 ...
Страница 132: ...LAARS Heating Systems Page 128 Fig 145 Burners and Combustion Chamber NT1000 ...
Страница 133: ...NeoTherm LC Boilers and Water Heaters Page 129 Fig 146 Burners and Combustion Chamber NT1700 ...
Страница 134: ...LAARS Heating Systems Page 130 Fig 147 Heat Exchanger Components NT1000 and NT1700 Fig 148 Burner Detail NT1000 ...
Страница 135: ...NeoTherm LC Boilers and Water Heaters Page 131 Fig 149 Burner Detail NT1700 ...
Страница 136: ...LAARS Heating Systems Page 132 Fig 150 Electronic Components Fig 151 Condensate Trap NT1000 ...
Страница 137: ...NeoTherm LC Boilers and Water Heaters Page 133 Fig 152 Condensate Trap NT1700 Fig 153 Flow Switch NT1000 and NT1700 ...
Страница 138: ...LAARS Heating Systems Page 134 This page intentionally left blank ...
Страница 139: ...NeoTherm LC Boilers and Water Heaters Page 135 This page intentionally left blank ...