LAARS Heating Systems
Page 32
The System pump connections are located on
terminal block 5 (5-6 on TB5) in the control panel.
(See Figure 20.) The System pump contacts are rated
for 120 VAC, 7.4 Amps. To use the contacts, power
must be supplied on one terminal with the other
terminal wired to the relay controlling the pump.
The DHW pump connections are located on terminal
block 5 (7-8 on TB5) in the control panel and are
rated for 120 VAC, 7.4 Amps. To use the contacts,
power must be supplied on one terminal, and the
other terminal wired to the relay controlling the
pump.
Additional 120 VAC circuits may be required for the
pumps.
7.3
24 VAC Transformer with Integral
Circuit Breaker
24 VAC is supplied by a transformer mounted on the
control panel. All 24 VAC power is supplied through
a circuit breaker that is part of the transformer. The
transformer is then connected to terminal blocks 1
and 2 (TB1 and TB2).
7.4
Signal Connections
See Section 9 for details on the following
connections:
• System sensor
• Call for heat/thermostat
• Outdoor air temperature sensor
• Aquastat for domestic hot water
• External control connections
7.5
Optional Field Connections
Optional components, such as low water cutoffs,
flow switches, additional high limits and other field
supplied devices can be installed as shown on the
wiring diagram (Fig. 22).
7.6 Ladder and Wiring Diagrams
See Figures 21 and 22.
Caution
When servicing controls, label all wires prior to
disconnection. Wiring errors can cause improper
and dangerous operation. Verify proper operation
after servicing
Table 10 - Electrical Data
Model
1,000
1,700
Voltage
120 V AC
120 V AC
Current - FLA
12 A
30 A
Current - Nominal
5 A
16 A
Содержание NTH1000
Страница 4: ...LAARS Heating Systems ...
Страница 11: ...NeoTherm LC Boilers and Water Heaters Page 7 Fig 6 Dimensions NT 1700 ...
Страница 37: ...NeoTherm LC Boilers and Water Heaters Page 33 Fig 21 Ladder Diagram ...
Страница 38: ...LAARS Heating Systems Page 34 Fig 22 Wiring Diagram ...
Страница 39: ...NeoTherm LC Boilers and Water Heaters Page 35 ...
Страница 51: ...NeoTherm LC Boilers and Water Heaters Page 47 Fig 51 Connection Terminals ...
Страница 128: ...LAARS Heating Systems Page 124 Fig 140 Machine Frame NT1000 13 3 Parts Illustrations ...
Страница 129: ...NeoTherm LC Boilers and Water Heaters Page 125 Fig 141 Rear Panel NT1000 Fig 142 Rear Panel NT1700 ...
Страница 130: ...LAARS Heating Systems Page 126 Fig 143 Machine Frame NT1700 ...
Страница 131: ...NeoTherm LC Boilers and Water Heaters Page 127 Fig 144 Front Panels and Covers NT1000 and NT1700 ...
Страница 132: ...LAARS Heating Systems Page 128 Fig 145 Burners and Combustion Chamber NT1000 ...
Страница 133: ...NeoTherm LC Boilers and Water Heaters Page 129 Fig 146 Burners and Combustion Chamber NT1700 ...
Страница 134: ...LAARS Heating Systems Page 130 Fig 147 Heat Exchanger Components NT1000 and NT1700 Fig 148 Burner Detail NT1000 ...
Страница 135: ...NeoTherm LC Boilers and Water Heaters Page 131 Fig 149 Burner Detail NT1700 ...
Страница 136: ...LAARS Heating Systems Page 132 Fig 150 Electronic Components Fig 151 Condensate Trap NT1000 ...
Страница 137: ...NeoTherm LC Boilers and Water Heaters Page 133 Fig 152 Condensate Trap NT1700 Fig 153 Flow Switch NT1000 and NT1700 ...
Страница 138: ...LAARS Heating Systems Page 134 This page intentionally left blank ...
Страница 139: ...NeoTherm LC Boilers and Water Heaters Page 135 This page intentionally left blank ...