• Turn off the call for heat, and set both
burners to run at 1200 RPM for low fire. Turn
on the call for heat, and check the performance
again.
20. If the CO
2
doesn’t track between the correct
limits, there is a possibility that one of the
burners has not been set up correctly. If
this occurs, repeat the setup procedure to
confirm that each burner is set up correctly.
If this condition persists, call the factory for
assistance. Before calling, be prepared to
supply the factory with the conditions at the
site where the boiler is installed - for example,
vent lengths, gas supply pressures with all
boilers operating, CO
2
and CO for each burner
individually and together, etc. Be able to
describe the ignition characteristics and the
color of the flame seen through the sight glass
of each burner.
21. When troubleshooting a burner setup, it is
sometimes helpful to watch the pressure
differential between the gas inlet and outlet.
To measure this, install a differential pressure
gauge capable of reading negative 0.01 inches
W.C. (0.002kPa). Attach the gauge to the
positive and negative ports shown in Fig. 104.
When the testing is complete, remove the
pressure gauge, and plug the ports. Repeat the
test setup on each burner.
Job P - Setting the Date and Time on the
System Display
(This is a Lead/Lag function – do this once for the whole Lead/
Lag system. Use the controller set up as the Lead/Lag Master –
usually the Primary controller on Boiler 1.)
The display acting as the Lead/Lag Master includes
an internal clock, which keeps track of the date and
time. This setting is important, because all of the
log entries for any Lockouts and Alerts include time
listings. If the Date and Time setting for the Lead/
Lag Master is not correct, the listings in the Lockout
and Alert logs will be incorrect.
The current version of the display does not include a
battery backup. This means that, if the boiler which
includes the display loses power, the Date and Time
setting for the system will be lost. (Any Faults or
Alerts recorded before the boiler lost power will
have the correct date and time listed.)
For this reason, it is important that you set the Date
and Time in two situations:
• When you first set up the Lead/Lag system.
• After each occasion when the power to the
boiler is interrupted.
Here is the procedure:
1. Start at the ‘home’ screen.
Fig. 107 – ‘home’ screen
2. Press the Setup button. The system will
present the Setup screen.
Fig. 108 – Setup Screen
3. Press the Display Setup button. The Display
Setup screen is shown in Fig. 106.
Fig. 109 – Display Setup Screen
Содержание NTH1000
Страница 4: ...LAARS Heating Systems ...
Страница 11: ...NeoTherm LC Boilers and Water Heaters Page 7 Fig 6 Dimensions NT 1700 ...
Страница 37: ...NeoTherm LC Boilers and Water Heaters Page 33 Fig 21 Ladder Diagram ...
Страница 38: ...LAARS Heating Systems Page 34 Fig 22 Wiring Diagram ...
Страница 39: ...NeoTherm LC Boilers and Water Heaters Page 35 ...
Страница 51: ...NeoTherm LC Boilers and Water Heaters Page 47 Fig 51 Connection Terminals ...
Страница 128: ...LAARS Heating Systems Page 124 Fig 140 Machine Frame NT1000 13 3 Parts Illustrations ...
Страница 129: ...NeoTherm LC Boilers and Water Heaters Page 125 Fig 141 Rear Panel NT1000 Fig 142 Rear Panel NT1700 ...
Страница 130: ...LAARS Heating Systems Page 126 Fig 143 Machine Frame NT1700 ...
Страница 131: ...NeoTherm LC Boilers and Water Heaters Page 127 Fig 144 Front Panels and Covers NT1000 and NT1700 ...
Страница 132: ...LAARS Heating Systems Page 128 Fig 145 Burners and Combustion Chamber NT1000 ...
Страница 133: ...NeoTherm LC Boilers and Water Heaters Page 129 Fig 146 Burners and Combustion Chamber NT1700 ...
Страница 134: ...LAARS Heating Systems Page 130 Fig 147 Heat Exchanger Components NT1000 and NT1700 Fig 148 Burner Detail NT1000 ...
Страница 135: ...NeoTherm LC Boilers and Water Heaters Page 131 Fig 149 Burner Detail NT1700 ...
Страница 136: ...LAARS Heating Systems Page 132 Fig 150 Electronic Components Fig 151 Condensate Trap NT1000 ...
Страница 137: ...NeoTherm LC Boilers and Water Heaters Page 133 Fig 152 Condensate Trap NT1700 Fig 153 Flow Switch NT1000 and NT1700 ...
Страница 138: ...LAARS Heating Systems Page 134 This page intentionally left blank ...
Страница 139: ...NeoTherm LC Boilers and Water Heaters Page 135 This page intentionally left blank ...