LAARS Heating Systems
Page 64
5.9 Outdoor Reset Adjustment
5.10 External Set Point Temperature Contro
l
Outdoor Reset varies the control setpoint based on
the outdoor temperature. The reset function works
as shown in Figure ‘CH Outdoor Reset’. When the
outdoor air temperature reaches
4:OH
“high outdoor
temperature setpoint”, the control point setting is
adjusted to
7:cL
“low boiler temperature setpoint”.
When the outdoor air temperature reaches
5:OL
“low
outdoor temperature setpoint” the control setpoint is
adjusted to
6:cH
“high boiler temperature”.
Default outdoor reset setpoint is 100°F (38°C)
A signal from a building management system may be connected to the appliance to enable remote
control. This signal should be a 0-10 volt DC signal. When this input is enabled, a building control
system can be used to control the set point temperature of the appliance.
The control interprets the 0-10 volt signal as follows; when the signal is between 0 and 1.5 volts, the
appliance will be in standby mode, not firing.
When the signal rises above 1.5 volts, the appliance will ignite. As the signal continues to rise
towards its maximum of 10 volts, the appliance will increase in set point temperature. Adjust
6:cH
and
7:cL
to set MIN and MAX boiler water temperatures respectively.
Connect a building management system or other auxiliary control signal to the terminals marked
for this purpose on the appliance terminal block (shown in Piping Diagrams, this manual). Caution
should be used to ensure that the 0-10 VOLT + connection does not become connected to ground.
Connect to terminal strip as outlined 4.17 Electrical Connections.
NOTE: 0 - 10VDC terminals may not be used for both outdoor reset and 0 - 10VDC temp
setpoint simultaneously.
The Outdoor Temperature Mode Icon on the display
will flash if an Outdoor Sensor or 0-10 Volt is not
connected to the appliance.
See
Figure 15
to set your Outdoor Reset. To check
the CH Target Temperature while using Outdoor
Temperature Mode,
Press the
button while the appliance is
operational and the display panel is powered on.
Connect to terminal strip as outlined 4.17 Electrical Connections.
NOTE: 0 - 10VDC terminals may not be used for both outdoor reset and 0 - 10VDC temp
setpoint simultaneously.
Figure 15.
Outdoor Reset
Operating condition
(warm weather shutdown)
Содержание mascot ft MFTHW
Страница 52: ...LAARS Heating Systems Page 50 4 19 Control Board Electrical Diagram Control Board ...
Страница 53: ...Mascot FT Heating Only Boiler Page 51 4 20 Ladder Diagram ...
Страница 71: ...Mascot FT Heating Only Boiler Page 69 6 2 Fault Tree Analysis 1 Flame detection ...
Страница 81: ...Mascot FT Heating Only Boiler Page 79 ...
Страница 83: ...Mascot FT Heating Only Boiler Page 81 ...
Страница 85: ...Mascot FT Heating Only Boiler Page 83 ...
Страница 87: ...Mascot FT Heating Only Boiler Page 85 ...
Страница 89: ...Mascot FT Heating Only Boiler Page 87 ...
Страница 91: ...Mascot FT Heating Only Boiler Page 89 ...
Страница 93: ...Mascot FT Heating Only Boiler Page 91 ...
Страница 94: ...LAARS Heating Systems Page 92 This page intentionally left blank ...
Страница 95: ...Mascot FT Heating Only Boiler Page 93 This page intentionally left blank ...