8.1 Annual startup & general maintenance
- Check the air vent
If the air vent valve seems to work freely without
leaking, replace cap “A” by twisting all the way on.
Loosen cap “A” one turn to allow vent to operate.
If vent does not operate correctly, replace the vent.
Maintenance procedures [Every 6 Months]
- Check the boiler piping (gas and water)
Visually inspect for leaks around internal water
piping. Also inspect external water piping,
circulators, relief valve and fittings. Immediately
call a qualified service technician to repair any
leaks. Leaks must be fixed by a qualified service
technician immediately.
Failure to comply with this instruction could result in
severe personal injury, death or substantial property
damage.
- Check the operate relief valve
Before proceeding the procedures, verify that relief
valve outlet has been piped to a safe place of
discharge, avoiding any possibility of scalding from
hot water. If water flows freely, release the lever
and allow the valve to seat. Watch the end of the
relief valve discharge pipe to ensure that the valve
does not weep after the line has had time to drain.
If the valve weeps, lift the seat again to attempt
to clean the valve seat. If the valve continues to
weep, contact your qualified service technician for
inspecting the valve and system. If water does not
flow from the valve even though you have lifted the
- Check the burner state
You can clean the exterior of burner. However, if you
need to clean the inside of the burner stage, you
should call an expert.
WARNING
Leaks must be fixed by a qualified service technician
immediately. Failure to comply with this instruction
could result in severe personal injury, death or
substantial property damage. This discharge line
must be installed by a qualified heating
installer or a service technician.
A
lever completely, the valve or discharge line may be
blocked. Shut down the Boiler immediately. Call your
qualified service technician to inspect the boiler and
system.
Содержание mascot ft MFTHW
Страница 52: ...LAARS Heating Systems Page 50 4 19 Control Board Electrical Diagram Control Board ...
Страница 53: ...Mascot FT Heating Only Boiler Page 51 4 20 Ladder Diagram ...
Страница 71: ...Mascot FT Heating Only Boiler Page 69 6 2 Fault Tree Analysis 1 Flame detection ...
Страница 81: ...Mascot FT Heating Only Boiler Page 79 ...
Страница 83: ...Mascot FT Heating Only Boiler Page 81 ...
Страница 85: ...Mascot FT Heating Only Boiler Page 83 ...
Страница 87: ...Mascot FT Heating Only Boiler Page 85 ...
Страница 89: ...Mascot FT Heating Only Boiler Page 87 ...
Страница 91: ...Mascot FT Heating Only Boiler Page 89 ...
Страница 93: ...Mascot FT Heating Only Boiler Page 91 ...
Страница 94: ...LAARS Heating Systems Page 92 This page intentionally left blank ...
Страница 95: ...Mascot FT Heating Only Boiler Page 93 This page intentionally left blank ...