Mascot FT, Heating Only, Boiler
Page 49
4.18 DIP Switches
System Control Setting
DIP switches 6 and 7 have to be set in the OFF position when the boiler is running normally.
DIP switches 1, 2, and 3 are system switches and are factory set to the boiler model and size
and should not be touched.
Maximum flame detecting voltage
2.4V
Pre-purge time Tp
Maximum 10s, minimum 1s
Safety Time (igniting time) Ts
1.5s
Igniting interval time
10s
Post-purge time Tip
120S (1st : 60s + 2nd 60s)
Over-heating 1,2,3 protection detection time
<2s
High & Low Water Level detection time
<5s
High & Low Water Level Recover time
<5s
Temperature sensor anomaly detection time
<3s
APS sensor detection time
<3s
Customer Service and Product Support:
800.900.9276 • Fax 800.559.1583
Headquarters:
20
Industrial Way, Rochester, NH, USA 03867 • 603.335.6300 • Fax 603.335.3355
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com
Litho in U.S.A. © Laars Heating Systems 1607 Document 4296B
800.900.9276
•
Fax 800.559.1583
(Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867
•
603.335.6300
•
Fax 603.335.3355
(Applications Engineering)
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8
•
905.238.0100
•
Fax 905.366.0130
www.Laars.com
Document 4296B
M
ascot FT, Heating Only, Gas Conversion Kit
pg 3 of 4
Figure C
Table B
DIP Switch Settings
MBH 80 100 120 140 N/A 199
9.
Per
Table B
, set DIP Switch
5 to OFF
for LP Propane.
10.
Turn
ON
the GAS and WATER supply to the Mascot FT.
11.
Turn
ON
the Mascot FT.
12.
Connect a manometer to the manifold pressure port. For dual port manometers, use the positive pressure
side. Check for proper manifold gas pressure. Refer to Table C.
ON
OFF
MIN
Fire
Normal Operation
MAX
Fire
Normal Operation
NG Natural
LP Propane
3” Vent Size
2” Vent Size
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
ON
Figure D
Gas Valve for
80 to 140 MBH
Gas Valve for
199 MBH
The gas valve on
the smaller models is
mounted vertically.
Manifold Pressure Port
Manifold Pressure Port
DO
N
OT
C H
A N
G E
REFE
RENCE
ON
LY.
Table C
Manifold pressure
Propane Gas (LP)
Natural Gas (NG)
MFTHW
80/100
-0.102
˝
WC
-0.102
˝
WC
0.00
˝
WC
0.00
˝
WC
MFTHW
120/140
-0.216
˝
WC
-0.216
˝
WC
0.00
˝
WC
0.00
˝
WC
MFTHW
175
-0.169
˝
WC
-0.129
˝
WC
-0.015
˝
WC
-0.015
˝
WC
MFTHW
199
-0.173WC
-0.134
˝
WC
-0.015
˝
WC
-0.015
˝
WC
CO
2
value
Propane Gas (LP)
Natural Gas (NG)
2˝ VENT
3˝ VENT
2˝ VENT
3˝ VENT
MFTHW
80/100
120/140/175/199
9.5~11%
8.5~10.5%
9~10.5 %
8~10%
Refer to the below table.
Manifold pressure
Propane Gas (LP)
Natural Gas (NG)
MFTHW
80/100
-0.102
˝
WC
-0.102
˝
WC
0.00
˝
WC
0.00
˝
WC
MFTHW
120/140
-0.216
˝
WC
-0.216
˝
WC
0.00
˝
WC
0.00
˝
WC
MFTHW
175
-0.169
˝
WC
-0.129
˝
WC
-0.015
˝
WC
-0.015
˝
WC
MFTHW
199
-0.173WC
-0.134
˝
WC
-0.015
˝
WC
-0.015
˝
WC
CO
2
value
Propane Gas (LP)
Natural Gas (NG)
2˝ VENT
3˝ VENT
2˝ VENT
3˝ VENT
MFTHW
80/100
120/140/175/199
9.5~11%
8.5~10.5%
9~10.5 %
8~10%
Refer to the below table.
13.
Establish a call for heat. You may need to disconnect the outdoor reset if you are making this gas
conversion during warm weather.
Содержание mascot ft MFTHW
Страница 52: ...LAARS Heating Systems Page 50 4 19 Control Board Electrical Diagram Control Board ...
Страница 53: ...Mascot FT Heating Only Boiler Page 51 4 20 Ladder Diagram ...
Страница 71: ...Mascot FT Heating Only Boiler Page 69 6 2 Fault Tree Analysis 1 Flame detection ...
Страница 81: ...Mascot FT Heating Only Boiler Page 79 ...
Страница 83: ...Mascot FT Heating Only Boiler Page 81 ...
Страница 85: ...Mascot FT Heating Only Boiler Page 83 ...
Страница 87: ...Mascot FT Heating Only Boiler Page 85 ...
Страница 89: ...Mascot FT Heating Only Boiler Page 87 ...
Страница 91: ...Mascot FT Heating Only Boiler Page 89 ...
Страница 93: ...Mascot FT Heating Only Boiler Page 91 ...
Страница 94: ...LAARS Heating Systems Page 92 This page intentionally left blank ...
Страница 95: ...Mascot FT Heating Only Boiler Page 93 This page intentionally left blank ...