LAARS Heating Systems
Page 34
4.10 Gas Supply Pressure
The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any
pressure testing of the system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve
during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
Loosen the pressure port bolts before you check the gas inlet pressure.
Inlet Gas Pressure Port
Manifold Pressure Port
Inlet Gas Pressure Port
Manifold Pressure Port
CAUTION
The minimum and maximum inlet gas line pressures must be
Natural Gas
LP Gas
Maximum Pressure
10.5˝ WC
Maximum Pressure
13.0” WC
Minimum Pressure
3.5˝ WC
Minimum Pressure
8.0” WC
Gas Valve
199 MBH
Gas Valve
80 - 140 MBH
Содержание mascot ft MFTHW
Страница 52: ...LAARS Heating Systems Page 50 4 19 Control Board Electrical Diagram Control Board ...
Страница 53: ...Mascot FT Heating Only Boiler Page 51 4 20 Ladder Diagram ...
Страница 71: ...Mascot FT Heating Only Boiler Page 69 6 2 Fault Tree Analysis 1 Flame detection ...
Страница 81: ...Mascot FT Heating Only Boiler Page 79 ...
Страница 83: ...Mascot FT Heating Only Boiler Page 81 ...
Страница 85: ...Mascot FT Heating Only Boiler Page 83 ...
Страница 87: ...Mascot FT Heating Only Boiler Page 85 ...
Страница 89: ...Mascot FT Heating Only Boiler Page 87 ...
Страница 91: ...Mascot FT Heating Only Boiler Page 89 ...
Страница 93: ...Mascot FT Heating Only Boiler Page 91 ...
Страница 94: ...LAARS Heating Systems Page 92 This page intentionally left blank ...
Страница 95: ...Mascot FT Heating Only Boiler Page 93 This page intentionally left blank ...