Digital Motor Protection Relay (GDR-M02) User's Manual (V1.00)
52 / 76
KyongBo Electric Co.,Ltd
Setting
(Menu)
3.Self-Diagnosis
Power, CPU Watchdog, Memory, Setting
4.RS-485
Comm.
1.Protocol
MODBUS
2.Baudrate
300, 600, 1200, 2400,
4800, 9600, 19200 (bps)
3.Slave Addr
1 ~ 254
5.System
Config.
1.Power
System
1.FREQ
50Hz or 60Hz
2.P_CT_RAT
5 ~ 10000 : 5 (5 Step)
3.G_CT_RAT
5 ~ 10000 : 5 (5 Step)
4.P_PT_RAT
0.1 ~ 3200.0 : 1 (0.1 Step)
2.T/S
Output
T/S
1~4
1.CON
OFF, PROT_OR, OCR,
Inst OCR, Time OCR, OCR_A,
OCR_B, OCR_C, OCR+OCGR,
OCGR, Inst OCR, Time OCR,
OVR+UVR, OVR, UVR,
NSOCR+RPR, NSOCR, RPR
2.RST
SELF or MANUAL
3.DLY
0.00~60.00Sec (0.01Sec Step)
3.Password
New Password : ****
6.Recorder
1.Display Faults
Counter, Element, Time,
Vab
∠
θ
º, Vbc
∠
θ
º, Vca
∠
θ
º,
Ia
∠
θ
º, Ib
∠
θ
º, Ic
∠
θ
º,
In
∠
θ
º, Iu(%)
2.Clear Faults
Clear All Faults? Yes or No
7.Test
1.Display Test
Are you sure to Display Test?
Yes or No
2.Contact Test
T/S 1~4, H.Alarm : On or Off