Digital Motor Protection Relay (GDR-M02) User's Manual (V1.00)
41 / 76
KyongBo Electric Co.,Ltd
Unit
Range
Step
Basis
Value
Reference
CURVE
OFF, NI, DT
-
NI
OFF, Inverse, Definite
Time Setting
PHASE
1, 3 PHASE
-
1 PHASE
Single Phase /
3 Phase Setting
PICK-UP
65 ~ 170V
1V
130V
Time Pickup Value
T-DIAL
0.1 ~ 10.0
0.1
10.0
Time Ratio Setting
DT-TIME
0.04 ~ 60.00Sec
0.01Sec
-
Definite Time Setting
【
Table 6.5
】
OVR Menu
6.1.7.6
Protection
▶
UVR Set Setting
This is to set Under Voltage Element. In Protection, select ( ) 6. UVR, display
follow.
- 〉
U V R
S e t
1 . C U R V E
:
D T
*
2 . P H A S E
: 1 P H A S E
3 . P I C K
-
U P
: 1 0 5 . 0 V
4 . T
-
D I A L
:
1 0 . 0
5 . R S T - M O D E
:
O F F
If you want to escape UVR, press the Key.
Detail menu of UVR is follow.