Digital Motor Protection Relay (GDR-M02) User's Manual (V1.00)
40 / 76
KyongBo Electric Co.,Ltd
- 〉
I N S T
O C G R
1 . M O D E
:
D T
*
2 . P I C K
-
U P
:
5 A
3 . D T
-
T I M E
:
0 . 0 4 s
If you want to escape INST. OCGR, press the Key.
Detail menu of INST. OCGR is follow.
Unit
Range
Step
Basis
value
Reference
MODE
OFF, INST, DT
-
DT
OFF, Inst, Definite
Time Setting
PickUp
2 ~ 50A
1A
5A
Inst. Pickup Value
DT-Time
0.04 ~ 60.00Sec
0.01Sec
0.04Sec
Defnite Time Setting
【
Table 6.4
】
INST. OCGR Menu
6.1.7.5
Protection
▶
OVR Setting
This is to set Over Voltage Element. In Protection, select ( ) 5. OVR, display
follow.
- 〉
O V R
S e t
1 . C U R V E
:
D T
*
2 . P H A S E
: 1 P H A S E
3 . P I C K
-
U P
:
6 5 . 0 V
4 . T
-
D I A L
:
0 . 1
If you want to escape OVR, press the Key.
Detail menu of OVR is follow.