Digital Motor Protection Relay (GDR-M02) User's Manual (V1.00)
16 / 76
KyongBo Electric Co.,Ltd
2.12 Negative-Sequence Current Element
Operation Value
Negative-Sequence 30 ~ 70% (1% step)
Operation Time
Characteristics
Definite
Time
0.04 ~ 60.00Sec (0.01Sec Step)
Release Delay Time
0.00 ~ 60.00Sec (0.01Sec Step)
Release Value
At least 95% of the Setting Value
Operation Value
Precision Ratio
Within ±5% of the Setting Value
【
Table 2.11
】
Negative-Sequence Current Element
2.13 Output Contacts
T / S1 Contacts (Trip contact) - 1a Contacts
Rated Voltage
AC 250V, DC 125V
Continuous Flow
Electricity Capacity
10A (AC 250V)
0.3 sec. Close
Circuit Capacity
30A (DC 125V)
Closing Capacity
6250VA
Material
Silver alloy
T / S2 ~ T / S4 Contacts (Signal contacts) - 3a Contacts
Rated Voltage
AC 250V, DC 125V
Continuous Flow
Electricity Capacity
5A (AC 250V)
0.3 sec. Close
Circuit Capacity
5A (DC 125V)
Closing Capacity
1250VA / 150W
Material
Gold-plate silver alloy
Healthy Alarm - 1b Contacts
Rated Voltage
AC 250V, DC 125V
Continuous Flow
Electricity Capacity
1A (AC 250V)
Open Circuit Capacity
DC 125V, 30W, Time constant(25ms), 1A
Closing Capacity
2500VA / 300W
Material
Silver alloy
【
Table 2.12
】
Output Contacts / Capacity