![Kyongbo Electric GDR-M02 Скачать руководство пользователя страница 18](http://html.mh-extra.com/html/kyongbo-electric/gdr-m02/gdr-m02_user-manual_2017068018.webp)
Digital Motor Protection Relay (GDR-M02) User's Manual (V1.00)
18 / 76
KyongBo Electric Co.,Ltd
2.15 Mechanical Test
Vibration
Vibration Response
10 ~ 150Hz, 0.5G, Front/Back, Left/Right,
Up/Down 1 time
Vibration Endurance
10 ~ 150Hz, 1G, Front/Back, Left/Right,
Up/Down 20 times
Shock
Shock Response
5G, Front/Back, Left/Right, Up/Down
3 times
Shock Withstand
15G, Front/Back, Left/Right, Up/Down
3 times
Bump
10G, Front/Back, Left/Right, Up/Down
100 times
Earthquake
1 ~ 8
㎐
x : 3.5mm, y : 1.5mm, Sweep : 1 time
8 ~ 35
㎐
x : 1G, y : 0.5G, Sweep : 1 time
【
Table 2.14
】
Mechanical Test
2.16 Noise Test
1MHz burst
disturbance
1MHz, 75ns,
400Hz, 2Sec
Common
mode
2.5kV
IEC60255-22-1
Differential
mode
1.0kV
EFT Burst
Applied Voltage
4kV
IEC60255-22-4
Repeated
Frequency
2.5kHz
Electrostatic
Discharge
Air discharge
8kV
IEC60255-22-2
Contact discharge
6kV
Lighting Surge
1.2/50
μ
s, 8/20
μ
s,
30sec, 3 times
Common
mode
2.0kV
IEC60255-22-5
Differential
mode
1.0kV
Radio Frequency
Radiation
Endurance
80MHz ~ 1GHz, 10V/m, 1sec
IEC60255-22-3
Radio Frequency
Conduction
Endurance
150kHz ~ 80MHz, 10V/m, 1sec
IEC60255-22-6
【
Table 2.15
】
Noise Test