Digital Motor Protection Relay (GDR-M02) User's Manual (V1.00)
45 / 76
KyongBo Electric Co.,Ltd
- 〉
P o w e r
S y s t e m
1 . F R E Q
:
6 0 H z *
2 . P _ C T _ R A T :
5 : 5
3 . G _ C T _ R A T :
1 . 0 : 1
4 . P _ P T _ R A T :
1 . 0 : 1
If you want to escape Power System., press Key. Exchange upper display.
System Config.
▶
Power system
▶
FREQ Setting
To use for relay of official frequency setting menu.
50Hz and 60Hz two unit, if power system frequency is 60Hz, select 60Hz.
System Config.
▶
Power system
▶
P_CT_RAT Setting
This manu set primary CT ratio of Phase. To set from 5 to 10000 with 5step.
This relay is designed 5A to secondary rated current CT, so, you must selcect 5A
to CT secondary rated current CT. For example, if you use 1000:5 CT,
P_CT_RAT set 1000.
System Config.
▶
Power system
▶
G_CT_RAT Setting
This manu set primary CT ratio of Ground side. To set from 5 to 10000 with
5step. This relay is designed 5A to secondary rated current CT, so, you must
selcect 5A to CT secondary rated current CT. For example, if you use 1000:5
CT, G_CT_RAT set 1000.
System Config.
▶
Power system
▶
P_PT_RAT Setting
This menu set primary PT ratio of Phase. To set from 0.1 to 3200.0 with 0.1step.
For example, if you use 22900:110 PT, P_PT_RAT set 208.2.
6.1.10.2 System Config.
▶
T/S Output Setting
T/S Output menu set connecting type and delay time of 4 contact output.
In System Config, select 2. T/S Output, T/S Output setting display follow.
- 〉