Digital Motor Protection Relay (GDR-M02) User's Manual (V1.00)
47 / 76
KyongBo Electric Co.,Ltd
System Config.
▶
T/S Output
▶
T/S 1
▶
2. RST Setting
This menu set to return method of contact output.
This relay has two method of Self Mode and Manual Mode.
Self Mode is auto retuning method and, Manual Mode is manual retuning method.
In other word, user want to contact output retuning, must push Reset ( ) Key.
System Config.
▶
T/S Output
▶
T/S 1
▶
3. DLY Setting
At contact output retuning, you can set delay time throw this menu.
This menu is applicable to Self Mode and if Manual Mode isn't applicable to the
menu.
If you DLY set 0.00, contact output return less than 40ms and if you want to
return less than 100ms, set 0.06.
You can set from 0.00 to 60.00 with 0.01Sec step, if you set less than 100ms,
error is ±35ms, if you set more than 100ms, error is ±5%.
6.1.10.3 System Config.
▶
Password Setting
This manu is to change password 4 position and each number set from 0 to 9.
In System Config., select 3.Password, password setting display follow.
- 〉
P a s s w o r d
N e w
P a s s w o r d
: * * * *
In this display, if you press ENTER ( ) Key after enter new password, come
out confirm new password display.
- 〉
P a s s w o r d
N e w
P a s s w o r d
: * * * *
C f m .
P a s s w o r d
: * * * *
In this display, enter new password agin and press ENTER ( ) Key, come out
under figure and exchange upper menu display.