![Kyongbo Electric GDR-M02 Скачать руководство пользователя страница 37](http://html.mh-extra.com/html/kyongbo-electric/gdr-m02/gdr-m02_user-manual_2017068037.webp)
Digital Motor Protection Relay (GDR-M02) User's Manual (V1.00)
37 / 76
KyongBo Electric Co.,Ltd
6.1.6 Measurement Display
Measurement display indicate measuring voltage and current.
Vab, Vbc, Vca mean line-to-line voltage, Ia, Ib, Ic mean phase current, In mean
zero-sequence current, Iu mean unbalanced current ratio and indicate magnitude and
angle.
That is, measuring data is primary values that are applied CT Ratio and PT Ration
by secondary values.
―
>
M e a s u r e m e n t s
V a b : 1 1 0 . 1
V ,
〈
0 . 0 º
V b c : 1 0 9 . 9
V ,
〈
2 3 9 . 8 º
V c a : 1 1 0 . 3
V ,
〈
1 2 0 . 2 º
I a :
5 . 0 3
A ,
〈
0 . 0 º
I b :
4 . 9 8
A ,
〈
2 4 0 . 1 º
I c :
5 . 0 0
A ,
〈
1 1 9 . 8 º
I n :
5 . 0 0
A ,
〈
0 . 0 º
I u :
0 . 0 0
%
If you want to escape Measurement Display, press Key. So, upper setting menu.
6.1.7 Protection Setting
Protection category has Time OCR, INST. OCR, Time OCGR, INST. OCGR, OVR,
UVR, NSOCR and RPR.
In Setting, select 2. Protection, display follow.
- 〉
P r o t e c t i o n
1 . T i m e
O C R
*
2 . I N S T
O C R
3 . T i m e
O C G R
4 . I N S T
O C G R
5 . O V R
6 . U V R
7 . N S O C R
8 . R P R
If you want to escape this menu, press Key. So, exchange main setting menu.
6.1.7.1
Protection
▶
Time OCR Setting
This is to set Time Over Current Element. In Protection, select ( ) 1. Time
OCR, display follow.