Kendrion Kuhnke Automation GmbH
AO4-U/I
83
11/25/2016
4.16.5.2 StateWord
Im Statuswort finden Sie die Meldungen über den Zustand des Moduls:
Bit
Name
Explanation
0
ResetErrorAck
Acknowledge of "Reset Error" in Module Control
1
Undervoltage24
Undervoltage 24V supply
2
EtherCATError
Sync Manager Watchdog
3
ConfigError
Sync Manager quantity structure does not match
4
-
5
-
6
-
7
-
8
Output 0 Overtemp
Output driver has recognized overtemperature (independent shutdown)
9
Output 1 Overtemp
Output driver has recognized overtemperature (independent shutdown)
10
Output 2 Overtemp
Output driver has recognized overtemperature (independent shutdown)
11
Output 3 Overtemp
Output driver has recognized overtemperature (independent shutdown)
12
Output 0 Open
no current detected in current mode (broken wire)
13
Output 1 Open
no current detected in current mode (broken wire)
14
Output 2 Open
no current detected in current mode (broken wire)
15
Output 3 Open
no current detected in current mode (broken wire)
4.16.5.3 Analog Outputs
Write the output values into the following variables:
Variable
Data type Explanation
Channel_n
UINT
Output value for channel n (n=0…3).
4.16.5.4 ControlWord
There is a control bit to quit the error messages.
Bit
Name
Explanation
0
ResetError
0 -> error events are saved, 1 -> errors are deleted after the event has gone
1-15
-
not used