Refer to IEC 61131-4, User's Guideline, for general installation instructions to be complied with
to ensure that hardware interface factors and the ensuing noise voltages are limited to tolerable
levels.
Interference Emission
Interfering emission of electromagnetic fields, HF
compliant to EN 55011, limiting value class A, Group 1
Information
If the controller is designed for use in residential areas, high-frequency emissions must comply
with limiting value class B as described in EN 55011.
Fitting the controller into earthed metal cabinets and installing filters in the supply lines may
produce a shielding compliant to the above standard.
General Notes on Installation
As component parts of machines, facilities and systems, electronic control systems must comply with
valid rules and regulations, depending on their field of application.
General requirements concerning the electrical equipment of machines and aiming at the safety of
these machines are contained in Part 1 of European Standard EN 60204 (corresponds to VDE 0113).
Electrical Immission Safeguard
To eliminate electromagnetic interference, connect the control system to the protective earth
conductor. Practice best cable routing.
Cable Routing and Wiring
Keep power circuits separate from control circuits:
DC voltages
60 V ... 400 V
AC voltages
25 V ... 400 V
Joint laying of control circuits is allowed for:
shielded data signals
shielded analogue signals
unshielded digital I/O lines
unshielded DC voltages < 60 V
unshielded AC voltages < 25 V
Location of Installation
Ensure that temperatures, contaminations, impact, vibration or electromagnetic interference are no
impediment to the installation.
Temperature
Consider heat sources such as general heating of rooms, sunlight, heat accumulation in assembly
rooms or control cabinets.