Kendrion Kuhnke Automation GmbH
AI4-Pt/Ni/TC
125
11/25/2016
4.21.4.3 Options
The following options can be set:
Name
Value
Explanation
SensorType
0
Off (default)
1
Internal (mV)
2
Pt100
3
Pt1000
4
Ni100
5
Ni1000 (DIN43760)
6
Thermo K
7
Thermo J
InputFormat
0
0,1°C
1
Ω / V
2
Raw (Raw value)
Data rate and
Filter
0
1000 measurements per second
1
600 measurements per second
2
330 measurements per second
3
175 measurements per second
4
90 measurements per second
5
45 measurements per second
6
20 measurements per second
7
20 measurements per 50 & 60Hz-filter
8
20 measurements per 50Hz-filter
9
20 measurements per 60Hz-filter
Average
n=1..255
Inputn= Average after n cycles (default=1)
4.21.4.4 StateWord
In the StateWord you can watch the state of the module:
Bit
Name
Explanation
0
ResetErrorAck
Acknowledge of "Reset Error" in Module Control
1
-
not used
2
EtherCATError
Sync Manager Watchdog
3
ConfigError
Sync Manager quantity structure does not match
4-7
-
not used
8
Input0low
Attached measured value in the wrong area
9
Input1low
Attached measured value in the wrong area
10
Input2low
Attached measured value in the wrong area
11
Input3low
Attached measured value in the wrong area
12-15
-
not used
16
Input0high
Attached measured value in the wrong area
17
Input1high
Attached measured value in the wrong area
18
Input2high
Attached measured value in the wrong area
19
Input3high
Attached measured value in the wrong area
20-31
-
not used
4.21.4.5 Analog Inputs
Die You find the digitalized input values in the following variables: