4.15.4 Technical data
Digital inputs .................................................. 4 (8)
DI0...3 ....................................................... 1ms
DI4 ............................................................ 0,1ms
DI5..7 ........................................................ 0,001ms
Counter (DI5) ................................................. 500kHz (up to 1 MHz)3
Digital outputs ................................................ 24
DO0..7:
0.5A
DO8..23: 0,1A
Analog Inputs ................................................. 4 x 0..10V
Resolution ...................................................... 12 Bit
Sampling rate ................................................ 1ms
RS485 ............................................................ electrically isolated
Baud rate ....................................................... 2,4…921,6 kBit/s
Termination .................................................... e.g. 4 x KDT 621 (9,6 or 19,2 kBit/s)
Connector IO/Power ...................................... Plug 36-pole
Controller ....................................................... ASIC ET1200
Baud rate ....................................................... 100 Mbit/s
Connector E-Bus ........................................... 10-pin system plug in side wall
End module ................................................... not required
Power supply ................................................. 24V DC -20% +25%
E-bus load...................................................... 90mA
Part no ........................................................... 694 444 62 CoE-Variant
Approvals: ......................................................
3
Value in brackets with ideal clock signal and ground