![Kuhnke FIO (V2) Скачать руководство пользователя страница 123](http://html.mh-extra.com/html/kuhnke/fio-v2/fio-v2_manual_2009572123.webp)
Kendrion Kuhnke Automation GmbH
AI4-Pt/Ni/TC
123
11/25/2016
4.21.4 Function 694 443 57 Kuhnke FIO AI4-Pt/Ni/TC
4.21.4.1 Note
The module 694 443 57 Kuhnke FIO AI4-Pt/Ni/TC is the not compatible successor of the following modules:
694 443 01
Ventura FIO AI4-Pt/Ni100
694 443 03
Ventura FIO AI4-Pt/Ni1000
694 443 05
Ventura FIO AI4-TE
The module is ETG-conform.
That means when an existing FIO block
694 443 01 Ventura FIO AI4-Pt/Ni100 or 694 443 03 Ventura FIO
AI4-Pt/Ni1000 or 694 443 05 Ventura FIO AI4-TE
shall be replaced by a
module 694 443 57 Kuhnke FIO
AI4-Pt/Ni/TC
the control program of the EtherCAT master must be changed.
.
4.21.4.2 Setting Options
The transformation of the analog signals can be executed DC-synchronous (Distributed Clocks) or SM-
synchronous (Sync Manager).
The access to the input values and the module status is done via process data objects that are mapped in
variables of the control program of the EtherCAT master.
For information and settings Service data objects are designed.