Kendrion Kuhnke Automation GmbH
Software
150
11/25/2016
6.2.2 Online Configuration
EtherCAT enables scanning of the devices in an Ethernet network. In the following example, the
configuration of the I / O block consisting of a Kuhnke controller 113, a Kuhnke FIO AI8-Pt / Ni / TC module
and a Kuhnke FIO AI8-I module shall be determined.
Connect the Kuhnke Controller 113 with the Kuhnke FIO AI8-I-module and the Kuhnke FIO AI8-
Pt/Ni/Tc-module and switch on the power supply.
Connect the Ethernet-interface of your PCs via CAT5-cable with your CoDeSys3-control Kuhnke
Controller 113. (
The cable can be both a patch cable and a crossover cable
.)
Start CoDeSys V3.
Open a project for your CoDeSys3-control Kuhnke Controller 113.
Highlight "Device (…..Kuhnke FIO Controller 113)" and select "Append device".
Configure an EtherCAT master by appending a device "EtherCAT Master" of 3S-Smart Software
Solutions GmbH to the device.
.
Highlight "Device (…..Kuhnke FIO Controller 113)" and start "Search network".
The Ethernet-network is scanned and
the connected CoDeSys V3 controller is found
.