Technical data
64
Burner does not switch of
at correct time
Check minimum boiler
temperature and type of
minimum delimiter => Protect
from corrosion
Burner will not switch on
Check boiler temperature
setting => The temperature
setting must be greater than
the boiler temperature.
Check operating mode =>
Standard
F
(test
B
)
With solar: Check burner
blocking (BOB)
Technical data
Malfunctions due to improper operation or settings are not
covered by the warranty.
EN 0608 6.6701.902-09 Printed
in Germany, Subjec
t to modification
Supply voltage to IEC 38
230 V AC
±
10%
Power consumption
Max. 8 VA
Switching capacity of the relays
250 V 2(2) A
Maximum current on terminal L1'
10 A
Enclosure to EN 60529
IP 40
Safety class II to EN 60730
Totally insulated
Switch panel installation in acc. with
DIN IEC 61554
Recess 138x92
Power reserve of the timer
>
10 hours
Permitted room temperature
during operation
0 to 50°C
Permitted room temperature
during storage
- 20 to 60 °C
Sensor resistances
Tolerance in ohms
Temperature tolerance
Tolerance in ohms
Temperature tolerance
Tolerance in ohms
NTC 5 k
Ω
(AF,KF,SPF,VF)
± -1% at 25°C
+/- 0.2K at 25°C
PTC 1010
Ω
(AFS,KFS,SPFS,VFAS)
± -1% at 25°C
+/- 1.3K at 25°C
PT1000 sensor with 1 k
Ω
+/- 0,2%
at 0 °C