Part 2: Overview of display values and settings
Expert
area
37
Installation (only for cascades via BUS)
Designation Value
range
Default
IV
DETECTED HSS
Display only
CAP/STAGE
00 – 9950 kW
00 kW
NEW CONFIG
00.01 (Off/On)
MIN MOD CASC
00 - 100
00
HW-BOILER
00 - 08
00
CONTROL DEV
[K]
Display
DES OUTPUT
0-100 [%]
Display
SWITCH VALUE
(-99) - 0 – (99) Display
BLOCK TIME
Remaining
[min]
Display
MAX T-HS
50°C – 110°C
90°C
DYN UPWARD
20 - 500 K
100 K
DYN DOWNWARD 20 - 500 K
100 K
RESET TIME
5 - 500
50
MODULAT MAX
0% - 100%
80 %
MODULAT MIN
0% - 100%
30 %
MIN MOD HS
0% - 100%
0 %
MODULAT DHW
40% - 100%
80 %
SEQUENCE 1
-
1 2 3 4 5 6 7 8
SEQUENCE 2
-
8 7 6 5 4 3 2 1
SEQU CHANGE
01 - 06
01
See following pages for continuation
DETECTED HSS (number of heat generators)
Display of heat generators automatically reported via BUS
with bus id (boiler no.)
CAP/STAGE (boiler output for each stage)
Display of the HS number and the stage => Selection with
Prog button => Input/Adjustment of HS output
- - - - = Stage/ Boiler not available
0 = Stage/ Boiler not active
In the case of boilers of the same power, a boiler release is
sufficient; e.g.:
HS
1 01
=> 01
HS
1 02
=> 01
HS
2 01
=> 01 etc.
(depending on the number of boilers)
Automatic assignment:
After restarting or after a new configuration, the controller
searches the bus systems for a heat generator. Within this
time period (approx. 2 min) no manual output entries are
allowed [Display „SCAN“]. In the case that a heat
generator answers with output information, this output is
automatically entered into the list. In the case that a heat
generator answers without output information, 15kW is
entered into the list. This value can then be adjusted
manually.