Expert area
Part 2: Overview of display values and settings
44
01 = Heating vis-à-vis buffer storage tank => F1, F3
ON: HS2-T > [F3 + HYST B 5K]
OFF: HS2-T < [F1 + HYST BURNER2]
02 = Heating vis-à-vis HW tank => F6
ON: HS2-T > [F6 + HYST B 5K]
OFF: HS2-T < [F6 + HYST BURNER2]
03 = Heating vis-à-vis STORAGE III (pool) => F15
ON: HS2-T > [F15 + HYST B 5K]
OFF: HS2-T < [F15 + HYST BURNER2]
Switching pattern
Switching the pump on is done if the temperature of the
solid fuel boiler exceeds the temperature of the Reference
sensor by the hysteresis (HYST B 5K).
Switching off occurs when the temperature drops 5K below
the switch-on temperature.
Start-up relief
Switching off occurs when the temperature of the solid fuel
boiler drops below the set limit temperature
(MIN T-HS2) by 5K. The pump is enabled again when the
temperature of the solid fuel boiler exceeds the set limit
temperature (MIN T-HS2).
Blocking HS1
ON:
T-HS2 > HS set tempe 5K and
pump HS2 = ON
OFF: T-HS2 <= HS set temperature or
pump WE2 = OFF
No HS1 blocking for
HS1 type = "Multi-stage switching“
HS1 type = "Multi-stage modulating“
STORAGE HS2 = "Heating against HW storage ( F6 )“
STORAGE HS2 = "Heating against STORAGE III ( F15 )“
!
If activated, the cooling function will also affect the
solid-fuel boiler function.
BUFFER (heater buffer storage type)
!
After activation (>0) it is not possible to connect a
FBR for heating circuit 1.
00 = no buffer storage for heating operation
01 = Buffer storage for heating operation (F1-F3)
(Sensor switching- in V1 no other function)
02 = Combination storage tank for heating and HW
operation
(Sensor switching- in V1 no other function)