Part 2: Overview of display values and settings
Expert
area
55
F15 FUNCTION (sensor function F15)
00 = Room sensor for heating circuit 2. If a further sensor
at the pulse input [IMP] is detected at this position an FBR
is evaluated.
01 = 0-10V input => For Preset Collector set temperature.
On evaluation see parameter V-CURVE in the
expert/installation level.
02 = light sensor (for plausibility testing with solar – no
function in version V1).
03 = 0-10V input preset for modulation. On evaluation see
parameter V-CURVE in the expert/installation level.