Part 1: Operation
Operation in normal mode
9
W
Service
(automatic reset after 15 min)
Boiler regulated at Boiler temperature = max. boiler
temperature= see page
34
; when the boiler temperature
has reached 65°C, the consumers are regulated to their
flow temperature to dissipate heat (cooling function).
!
The cooling function must be explicitly enabled in
the consumer circuits by means of a set value.
Effect of the operating mode
The operating mode set here affects the boiler regulation
and the integrated heating circuits of the controller.
Each heating circuit can be assigned a separate operating
mode from the one set by means of the "operating mode"
parameter in the user level of the corresponding heating
circuit.
When the "
i
= Standby/OFF", and "
F
= Summer mode"
operating modes are set, they have a reducing effect on
system controllers with respect to all heating circuits and
consumer circuits in the entire system.
!
For mixer controllers the reduction of operating
mode is only effective for internal heating circuits.