Expert area
Part 2: Overview of display values and settings
34
00 = OFF => The resistor is not set
01 = ON
=> The resistor is set
EBUS SUPPLY (supply for eBUS)
Switching the eBUS supply on / off in relation to connected
devices (power supply balance) => see part 3:
Description of functions – eBUS burner controls.
TIME MASTER
(Only without or TIME MASTER in system)
00 no time master => each heating circuit has its own time
01 controller is time master => all controllers and remote
controls take over the time settings of this controller.
!
No more than 1 TIME MASTER is permitted in the
system!
MAX T-HS1/2 (Max. temperature HS)
Protects the HS from overheating / prevents triggering the
LIMITER.
!
Caution: Also works with hot water preparation.
MIN T-HS1/2 (min temperature HS)
Decreased condensation build-up in HS with low heat
requirements. Switching the HS off is always done earlier
when achieving the HS minimum temperature MIN T-HS +
HYSTERESIS (Standard 5K)
(see MIN DELIMI as well).
MAX/MIN T-HEADER (only for cascades)
See MAX/MIN T HS1/2.