Multicheck6010
EN
- 89 -
Trip-out time
Range (ms)
Resolution (ms)
Accuracy
0.0
÷
300.0
1
±3 ms
Contact voltage
Range (V)
Resolution (V)
Accuracy
0.0
÷
9.9
0.1
(-0 % / +10 %) of r 5 digits
10.0
÷
99.9
0.1
(-0%/+10%) of reading
6.4 Fault loop impedance and prospective fault current
Zloop L-PE, I
pfc
sub-function
Measuring range according to EN61557-3 is 0.25 Ω
÷
1999 Ω.
Range (Ω)
Resolution (Ω)
Accuracy
0.2
÷
9999
(0.20 ... 19.99)
0.01
(20.0 ... 99.9)
0.1
(100 ... 9999)
1
±(5 % of r 5 digits)
Prospective fault current (calculated value)
Range (A)
Resolution (A)
Accuracy
0.00
÷
19.99
0.01
Consider accuracy of fault loop
resistance measurement
20.0
÷
99.9
0.1
100
÷
999
1
1.00k
÷
9.99k
10
10.0
÷
100.0k
100
Test curent (a 230 V)
3.4 A, Sine wave 50Hz (10 ms ≤ t
LOAD
≤ 15 ms)
Nominal voltage range
93 V
÷
134 V; 185 V
÷
266 V (45 Hz
÷
65 Hz)
Zloop L-PE RCD, I
pfc
, non trip subfunction
Measuring range according to EN61557 is 0.46 Ω
÷
1999 Ω.
Range (Ω)
Resolution (Ω)
Accuracy*
0.4
÷
19.99
(0.40 ... 19.99)
0.01
±(5 % of r 10 digits)
20
÷
9999
(20.0 ... 99.9)
0.1
(100 ... 9999)
1
±10 % of reading
*) La precisión puede verse afectada en caso de un fuerte ruido en la tension de la red.