Multicheck6010
EN
- 61 -
3.5 Sound warnings
Short high sound button pressed
Continued sound during continuity test when result is <35 Ohm
Upwards sound attention, dangerous voltage applied
Short sound power off, end of measurement
Downwards sound warnings (temperature, voltage at input, start not possible)
Periodic sound
Warning!
Phase voltage on the PE terminal! Stop all the measurements
immediately and eliminate the fault before proceeding with any activity!
3.6 Performing measurement
3.6.1 Measurement function/ sub-function
The following measurements can be selected with the function selector switch:
•
Voltage/rotation/frequency measurement
•
Earth resistance
•
R Low
• R Insulation
• Line impedance
•
Loop (Loop RCD) impedance
•
RCD
The function/sub-function name is highlighted on the display by default.
3.6.2 Selecting measurement function/ sub-function
Using navigation keys
▲▼
select the parameter/limit value you want to edit. By using
◀▶
keys
the value for the selected parameter can be set.o.
Once the measurement parameters are set, the settings are retained until new changes are
made.
3.6.3 Performing tests
When symbol is displayed test can be started by pressing the “TEST” button. After completion
of the test its result value and status will be displayed. In case of PASSED measurement, result
value will be displayed in black color along with the status symbol. In case of NOT PASSED
measurement, the result value will be marked in red color along with the symbol.
3.7 Setup menu
To enter the
Setup
menu, press the SETUP key. In the
Setup
menu, the following actions can be
taken:
•
Isc factor:
Set prospective short/fault current scaling factor
•
Date/Time:
Set internal date and time
•
Start function:
Selected function will start when switched on
•
RCD standard:
Select national standard for RCD testing, e.g EN61008 or BS7671
•
ELV:
Select voltage for ELV warning.
•
Power off time:
Select time when device should switch off if not used.
•
Cont timeout:
Select time-out when measurement should stop automatically.
•
ISO timeout:
Select time-out when measurement should stop automatically.
•
Supply system:
Select supply network/system, e.g. TN or IT.
•
Device info:
Shows info about device, e.g. Firmware version