4.4 Fault loop impedance and prospective fault current
The loop impedance function has two sub-functions available:
LOOP IMPEDANCE
sub-function performs a fast fault loop impedance measurement on supply
systems which do not contain RCD protection.
LOOP IMPEDANCE RCD
trip-lock sub-function performs fault loop impedance measurement on
supply systems which are protected by RCDs
4.4.1 Fault loop impedance
How to perform fault loop impedance measurement
Step 1
Select the LOOP function with the function selector FCT key and select the
LOOP
mode with the
▲▼
and
◀▶
navigation keys. Then select desired
Type, Time and Curr
option values with the
▲▼
and
◀▶
navigation keys. The following menu is displayed:
Figure 4 21: Loop impedance measurement menu
Step 2
Connect the test leads to the instrument and follow the connection diagram shown in
the figure 4.22 to perform fault loop impedance measurement.
Figure 4 22: Connection of plug cable and universal test cable
Step 3
Check for any warnings displayed on the screen and check the online voltage/terminal
monitor before starting the measurement. If everything is ok and the is shown, press
the TEST key. After performing the measurement, the test results will appear on the
display.