- 67 -
Figure 4 10: Example of Low current continuity measurement result
Displayed result:
R
Low current continuity resistance result
I
Current used in the measurement
Warning:
•
Low current continuity measurement should only be performed on de-energized objects!
Notes:
•
If a voltage of higher than 10 V exists between test terminals, the continuity measurement will not
be performed.
•
Before performing a continuity measurement, compensate for the test lead resistance (if
necessary). The compensation is performed in
Continuity
sub- function
R LowΩ
.
4.3 Testing RCDs
When testing RCDs, the following sub-functions can be performed:
•
Contact voltage measurement,
•
Trip-out time measurement,
•
Trip-out current measurement,
•
RCD autotest.
In general, the following parameters and limits can be set when testing RCDs:
•
Limit contact voltage,
•
Nominal differential RCD trip-out current,
•
Multiplier of nominal differential RCD trip-out current,
•
RCD type,
• Test current starting polarity.