4.3.1 Contact voltage
How to perform contact voltage measurement
Step 1
Select the
RCD
function with the FCT key and select the
Uc
mode with the
▲▼
and
◀▶
navigation keys. The following menu will be displayed:
Figure 4 11: Contact voltage measurement menu
Step 2
Set the following measuring parameters and limit values:
•
I
ΔN
: Nominal residual current
•
Tipo
: RCD type,
•
Límite
: Limit contact voltage.
Step 3
Connect the test leads to the instrument and follow the connection diagram shown in
figure 4.12 to perform contact voltage measurement.
Figure 4 12: Connection of plug test cable or universal test cable
Step 4
Check for any warnings and check the online voltage/terminal monitor on the display
before starting the measurement. If everything is ok and the is shown, press the
TEST key. After performing the measurement, the results appear on the display
together with the
or indication.