RUN THE GAS LINE
CAUTION: Installation of the gas line must only be done by a qualified person in accordance with local
building codes.
The conversion shall be carried out in accordance with the requirements of the provincial authorities having
jurisdiction and in accordance with the requirements of the ANSI Z223.1 installation code.
LP Gas Conversion Kit #OCK-H55N - used to convert a Natural Gas millivolt board to LP Gas.
If a gas conversion is necessary, one of the following conversions kits must be used:
Natural Gas Conversion Kit #OCK-H42N - used to convert an LP Gas millivolt board to natural gas.
GAS CONVERSIONS
NOTE: This unit is equipped with a 3/8" x 12” long flexible gas connector and manual shut off valve.
NOTE: The gas line should be run to the point of connection where the shut-off valve and flexible gas line will
connect.
CAUTION:
The manual shut-off valve or flexible gas tubing must not extend outside of the unit cavity. See the
WARNING label affixed to the flexible tubing for additional installation instructions and warnings.
NOTE: For high altitude installations consult the local gas distributor or the authority having jurisdiction for
proper rating methods.
Orifice size: 55 Input: 19,000 BTU/hr.
Efficiency: 66.2%
AFUE: 65.30%
Minimum input: 14,000 BTU/hr
P4-AFE: 55.53%
IMPORTANT:
The efficiency rating of this appliance is a product thermal efficiency rating determined
under continuous operating conditions and was determined independently of any installed system. To
maintain proper efficiency, the pilot must be shut off when this fireplace is not in operation.
Page 14
Manifold Pressure (lo setting): 5.4 inches W.C.
Manifold Pressure: 10.0 inches W.C.
The maximum inlet gas supply pressure: 13.0 inches W.C.
The minimum inlet gas supply pressure: 11.0 inches W.C. (recommended)
LP GAS:
Manifold pressure: 3.5 inches W.C.
Manifold pressure (lo setting): 1.7 inches W.C.
Orifice size: 42 Input: 23,000 BTU/hr.
Efficiency: 69.1%
AFUE: 68.4%
Minimum input: 16,000 BTU/hr
P4-AFE: 56.1%
The minimum inlet gas supply pressure: 5.0 inches W.C. ( 7.0 inches W.C. recommended)
The maximum inlet gas supply pressure: 10.5 inches W.C.
NATURAL GAS: