Accessing Internal Components 

This chapter contains important information that you must read before accessing the internal components. You must 
follow these procedures properly when installing, removing or handling any system component. 

It is recommended to expand your system with additional PCI/PCIe/PCIe Mini cards before it is installed into an 
industrial control cabinet. Please consider following instructions when you install or remove expansion cards. 

 

Before installing/removing an expansion card, please pay attention to the following information: 

 

 

Please observe the “General Safety Instructions for IT-Equipment” provided with the system 
(refer also to the chapter 1/) and the installation instructions contained in this manual. The 
KBox C-102 system shall be mounted into a control cabinet.  
Only personnel with appropriate qualifications, trainings and authorization are permitted to 
install and work with the KBox C-102 system. 
The installation/removal of HDDs/SSDs and/or expansion cards may only be performed by 
a qualified person, according to the description in this manual. 
Before removing the cover of the device, make sure that the device is powered off and 
disconnected from the power supply. 
Before you upgrade the KBox C-102 with expansion cards, pay attention to the power 
specifications in chapter 16/ “Technical Specifications” and make sure that the power 
consumption of the expansion cards does not exceed 15 W per card.

 

 

 

 

Please follow the safety instructions for components that are sensitive to electrostatic 
discharge (ESD). Failure to observe this warning notice may result in damage to the device 
or/and internal components. 

 

 

 

Please pay attention to the manufacturer’s instructions before installing/removing an 
expansion card. 

 

 

Содержание KBox C-102 Series

Страница 1: ...USER GUIDE www kontron com 1 KBox C 102 Doc User Guide Rev 1 0 Doc ID 1062 4961 KBox C 102 4 KBox C 102 2 KBox C 102 1 KBox C 102 0...

Страница 2: ...KBox C 102 User Guide Rev 1 0 www kontron com 2 This page has been intentionally left blank...

Страница 3: ...be suitable for the specified use without further testing or modification Kontron expressly informs the user that this user guide only contains a general description of processes and instructions whi...

Страница 4: ...s is entirely at your risk To minimize the risks associated with your products and applications you should provide adequate design and operating safeguards You are solely responsible for compliance wi...

Страница 5: ...to the corporate offices contact information on the last page of this user guide or visit our website CONTACT US Customer Support Find Kontron contacts by visiting http www kontron com support Custome...

Страница 6: ...cribed by the law may endanger your life health and or result in damage to your material ESD Sensitive Device This symbol and title inform that the electronic boards and their components are sensitive...

Страница 7: ...before performing any work on this product Earth ground connection to vehicle s chassis or a central grounding point shall remain connected The earth ground cable shall be the last cable to be discon...

Страница 8: ...oduct then re pack it in the same manner as it was delivered Special care is necessary when handling or unpacking the product See Special Handling and Unpacking Instruction Quality and Environmental M...

Страница 9: ...19 2 3 EMC Compliance Canada 19 3 Shipment and Unpacking 20 3 1 Unpacking 20 3 2 Scope of Delivery 20 3 2 1 Optional Parts System Expansion 20 3 2 2 Optional System Extension 20 3 3 Spare Parts 20 3...

Страница 10: ...Module 48 6 3 2 mSATA Socket 48 6 3 3 Expansion Socket for PCIe Mini Cards 49 6 3 4 Riser Cards Expansion Sockets for PCI PCIe Cards 49 6 3 5 Installing Removing PCI PCIe Expansion Cards for KBox C 1...

Страница 11: ...tup Script 108 15 2 3 Examples of Startup Scripts 109 15 3 Updating the uEFI BIOS 110 15 3 1 uEFI BIOS Recovery 111 15 3 2 Determining the Active Flash 111 16 Technical Specifications 112 16 1 Mechani...

Страница 12: ...28 Table 4 Status and General Purpose LEDs 32 Table 5 Maximum Temperatures 53 Table 6 Navigation Hot Keys Available in the Legend Bar 78 Table 2 Main Setup Menu Sub screens and Functions 80 Table 3 Ad...

Страница 13: ...ternally accessible battery shown with removed protective cover 25 Figure 6 Bottom side view 27 Figure 7 Right side view 27 Figure 8 Front side view config with removable drives 27 Figure 9 Front side...

Страница 14: ...tray and removed air filter 66 Figure 54 Filter mat Holder without air filter 66 Figure 55 Holder shown for a KBox C 102 2 with air filter 66 Figure 56 Air filter shown for a KBox C 102 2 66 Figure 57...

Страница 15: ...igure 92 Dimensions top side KBox C 102 1 120 Figure 93 Dimensions right side KBox C 102 1 with fan tray option 121 Figure 94 Dimensions front side with key holes KBox C 102 1 with fan tray option 121...

Страница 16: ...t sufficient air circulation is available to cool the product please ensure that the ventilation openings are not covered or blocked If an air filter is provided this should be cleaned regularly Do no...

Страница 17: ...ndirectly a reliable protective earthing connection is provided a suitable easily accessible disconnecting device is used in the application e g overcurrent protective device if the device itself is n...

Страница 18: ...lways handle electrostatically sensitive components by their edge or by their casing 4 Avoid contact with pins leads or circuitry 5 Turn off power and input signals before inserting and removing conne...

Страница 19: ...If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interferenc...

Страница 20: ...s System Expansion Front accessible drive bays for 2 5 SATA HDD SSDs Mini PCIe cards mSATA cards MO 300 PCIe cards 3 2 2 Optional System Extension RS232 RS422 Port via internal factory mounted and con...

Страница 21: ...ion Product Identifikation KBox C KBox C 102 KBox C 102 4 corresponds for system configurations with four slot rows for optional removable DRIVEs and or PCIe expansion slots KBox C 102 2 corresponds f...

Страница 22: ...lus a comprehensive optionally available IOs and devices Basic version without additional fan and or HDD and or battery only The KBox C 102 offers a maintenance free Wartungsfrei operation That means...

Страница 23: ...le DisplayPort or Long Distance Solution LDT3 via corresponding internal factory mounted adapter modules Optional external accessible RTC lithium battery Optional system extension with fan tray not po...

Страница 24: ...perature If the time is not valid this is indicated by a status bit in the RTC registers For details see the RV 8803 C7 application manual To get the maximum buffer time it is necessary to have the sy...

Страница 25: ...10 1 Replacing the Lithium Battery The protective cover of the KBox C 102 with externally accessible lithium battery must always be installed during transportation and operation activities The protect...

Страница 26: ...subsections 6 3 2 and 6 3 7 Refer to chapter 16 Technical Specifications and the descriptions in this manual 4 3 3 Standard PCI Express Interfaces The baseboard of KBox C 102 provides 1x PCIe x8 inter...

Страница 27: ...re 12 Views of a KBox C 102 2 Figure 6 Bottom side view Figure 7 Right side view Figure 8 Front side view config with removable drives Figure 9 Front side view config without removable drives Figure 1...

Страница 28: ...ELDBUS X205 or X206 1x 1x 1x 1x CAN Port X203 1x 1x 1x 1x RS232 RS422 Port X204 1x 1x 1x 1x LDT3 X201 or DisplayPort DP 2 X202 1x 1x 1x 1x C PCI PCIe Expansions via corresponding Riser Cards Options 1...

Страница 29: ...th status LEDs Activity link green link up green blinking activity Speed off green yellow 10 100 1000 Mbit s For pin assignment refer to subsection 18 1 2 4 4 3 X105 X106 USB 3 0 The KBox C 102 provid...

Страница 30: ...access while the SD LED Figure 18 is flashing To install a card please perform following steps 1 Insert the SD SDHC SDXC card into the SDCARD slot marked SDCARD see Figure 59 and Figure 15 on the fron...

Страница 31: ...trol of the operating system Once the system has been shut down it can restarted by pressing the PWR button assuming that power is still applied to the main input power connector X101 4 4 9 RESCUE But...

Страница 32: ...nd Figure 18 Figure 18 Detail Status and General Purpose LEDs Table 4 Status and General Purpose LEDs Status and General Purpose LEDs Designator Function Color Description THERM Thermal Green Normal o...

Страница 33: ...that KBox C 102 4 supports up to 4x PCIe x4 PCIe x1 expansion cards For system configuration refer to Figure 59 Figure 58 and for expansion cards installation refer to the subsection 6 3 5 Installing...

Страница 34: ...102 2 configuration with removable 2 5 SATA HDDs SSDs was ordered no installation of any internal SATA HDD SSD with mounting frame is possible Refer also to the area marked D in the section 4 4 Figure...

Страница 35: ...rm the following steps 1 Pull out the lever Figure 21 pos 3 of the drive cover Figure 20 pos 2 and release it If required unlock the lever with the corresponding key before 2 The drive bay cover will...

Страница 36: ...e the cooling fins to the chassis 9 Type label 10 Hole for further system fan tray extension 11 Air intake openings on the bottom cover 12 Air exhaust openings on the top cover Please do not remove th...

Страница 37: ...1 6 Mechanical Specifications of the KBox C 102 1 with Fan Tray Option Figure 27 Rear side of the KBox C 102 2 system 4 8 Functional Earth Stud There is an M4 functional earth terminal on the lower m...

Страница 38: ...or Profinet via internal factory mounted adapter module You have to order these components separately in order to extend your KBox C 102 at the factory Example of system configuration see below Figur...

Страница 39: ...Box C 102 can be extended via an adapter module with a CAN port that allows you CAN Bus communication The optional CAN port Figure 28 Figure 29 pos 2 is implemented as a sub D 9 pin connector male Thi...

Страница 40: ...206 for Profinet will be used Only one of these two Fieldbus interfaces D Sub or dual RJ45 can be ordered as optional extension of your KBox C 102 system Figure 30 X205 or X206 Locations for the optio...

Страница 41: ...tray Figure 31 pos 1 with one fan as well as the air filter Figure 31 KBox C 102 1 equipped with the optional fan tray The fan is integrated in a user friendly replaceable fan tray hot swapping The f...

Страница 42: ...is should only be carried out by qualified personnel aware of the associated dangers see subsection 10 3 Replacing the Fan Tray Figure 32 Fan tray components of the KBox C 102 1 2 4 cable connections...

Страница 43: ...02 system shall be mounted into a control cabinet Only personnel with appropriate qualifications trainings and authorization are permitted to install and work with the KBox C 102 system The installati...

Страница 44: ...ed to the chassis using the centring bracket at the rear side of the cover Figure 33 pos 3 and the fixing bracket with captive knurled screws at the front side of the cover Figure 33 pos 5 When insert...

Страница 45: ...instructions contained in the chapter 8 Installation Instructions 1 Close all applications Shut down the system properly and disconnect the connection to the power source Disconnect all peripherals 2...

Страница 46: ...l the right side cover out to detach it from the sideways mounted bolts Put the right side cover and the screws aside for later use Figure 37 KBox C 102 2 without top and right side cover shown with a...

Страница 47: ...the removable HDDs SSDs 8 Lower mounting bracket with key holes 9 SATA cable connections power and data 10 Baseboard 11 2x mSATA sockets 12 Mechanical fixing assemblies for 2x 2 5 mSATA SSD and 1x PCI...

Страница 48: ...s 6 Cover retaining plate on the rear side 7 Mechanical fixing assemblies for 2x 2 5 mSATA SSD two fixing clips for each mSATA SSD 8 Upper mounting bracket with key holes 9 Cooling fins Refer to the i...

Страница 49: ...of PCI PCIe cards into from the corresponding socket Figure 40 pos 5 and pos 6 Figure 41 pos 5 and pos 8 and Figure 63 pos 12 please refer to the subsection 6 3 5 Installing Removing PCI PCIe Expansio...

Страница 50: ...kets you have to open the KBox C 102 4 2 1 as described in the section 6 2 Opening and Closing the KBox C 102 step 1 6 3 To remove install an expansion card you have to remove the corresponding card s...

Страница 51: ...card please proceed according to the steps described 1 Close all applications shut down the system properly and disconnect the connection to the power source Disconnect all peripherals 2 Open the dev...

Страница 52: ...ips 6 In order to close the KBox C 102 proceed in reverse order step 6 to 1 of the section 6 2 To remove an mSATA SSD please proceed according to the steps described 1 Close all applications shut down...

Страница 53: ...4 2 1 The optional fan tray extension allows to operate the system at higher ambient temperature conditions and provides a higher air flow through the chassis providing a better cooling of the system...

Страница 54: ...igher than the ambient temperature An approximately internal temperature rise is given 7 7 Processor Thermal Monitoring The processor used with the KBox C 102 system provides internal thermal monitori...

Страница 55: ...rmitted to install and work with the Kontron KBox C 102 This device shall only be installed in or connected to systems that fulfill all necessary technical and specific environmental requirements The...

Страница 56: ...ther devices within the keep out area The clearances of 50mm and 100mm around the KBox C 102 must be observed refer to the marked areas in Figure 43 to Figure 49 Figure 43 Keep out area for mounting a...

Страница 57: ...uide Rev 1 0 www kontron com 57 Figure 45 Keep out area for mounting around KBox C 102 2 front side view without fan tray Figure 46 Keep out area for mounting around KBox C 102 2 front side view with...

Страница 58: ...uide Rev 1 0 www kontron com 58 Figure 47 Keep out area for mounting around KBox C 102 1 front side view without fan tray Figure 48 Keep out area for mounting around KBox C 102 1 front side view with...

Страница 59: ...KBox C 102 User Guide Rev 1 0 www kontron com 59 Figure 49 Keep out area for mounting around KBox C 102 0...

Страница 60: ...rting the 0V wire 8 2 1 Cabling For the pin assignment Phoenix power plug terminal refer to the subsection 4 4 1 X101 Power Input Connecto 1 Cut the required length three isolated wires 1 mm2 AWG18 an...

Страница 61: ...rned off via the power button Figure 59 Figure 61 Figure 64 and Figure 17 marked PWR parts of the system are still energized The disconnecting device fuse circuit backer rating must be in accordance w...

Страница 62: ...f data or other undesirable effects 9 3 Operating System and Hardware Component Drivers Your system can be supplied optionally with a pre installed operating system If you have ordered your KBox C 102...

Страница 63: ...in them for later use 3 Remove the lithium battery from the holder by pulling it outwards 4 Place a new lithium battery in the battery holder 5 Pay attention to the polarity of the battery as shown in...

Страница 64: ...ed out by qualified personnel aware of the associated dangers The fan will not stop immediately when the fan tray is removed during operation Pull out the fan tray only a few centimeters and wait unti...

Страница 65: ...for later reassembly refer to step 2 and 3 in Figure 52 4 Remove the soiled air filter Figure 52 pos 3 and Figure 53 pos 6 5 Clean the air filter as follows 6 Rinse in water up to approx 40 C possibl...

Страница 66: ...Figure 55 Holder shown for a KBox C 102 2 with air filter Figure 56 Air filter shown for a KBox C 102 2 1 KBox C 102 assembled with the optional fan tray slot 2 Removed fan tray 3 Fan tray slot withou...

Страница 67: ...e drive bays and without mounting brackets 1 Side of KBox C 102 4 with cooling fins 2 Top side cover with knurled screws 2 1 THERM DRIVE SD WD GP1 GP2 GP3 GP4 PCIe Slot 3 PCIe Slot 4 Drive Bay 2 SATA...

Страница 68: ...l ext interfaces and onboard components Onboard controller Complex function PWR LED Power Button RSQ LED System EPROM SPI Flash RESCUE BIOS I 2 C SPI Gold CAP RTC Ultra low power Temperature Sensor I2...

Страница 69: ...ith removable drive bays and without mounting brackets 1 Side of KBox C 102 2 with cooling fins 2 Top side cover with knurled screws THERM DRIVE SD WD GP1 GP2 GP3 GP4 PCIe Slot 2 PCIe Slot 1 Drive Bay...

Страница 70: ...Type 6 Module Baseboard COMe Module Onboard connectors External interfaces Optional ext interfaces and onboard components Onboard controller Complex function PWR LED Power Button RSQ LED System EPROM...

Страница 71: ...front view shown with removable drive bay without mounting brackets 1 Side of KBox C 102 1 with cooling fins 2 Top side cover with knurled screws 1 X 110 RS232 SD Card X 107 X 108 USB 2 0 X105 X106 US...

Страница 72: ...Onboard connectors External interfaces Optional ext interfaces and onboard components Onboard controller Complex function PWR LED Power Button RSQ LED System EPROM SPI Flash RESCUE BIOS I 2 C SPI Gol...

Страница 73: ...scription in the subsection 4 5 Left and Right Side View is valid also for KBox C 102 1 Figure 63 Inside of the KBox C 102 1 shown with a removable HDD 1 COM Express module 2 Baseboard 3 Mechanical fi...

Страница 74: ...ce of the KBox C 102 1 system if internal or external accessible supports speeds of up to SATA 6 Gb s This SATA interface supports hot swapping To prevent data loss don t remove the HDD SSD during rea...

Страница 75: ...ns Figure 64 KBox C 102 0 front view shown without mounting brackets 1 Side of KBox C 102 0 with cooling fins 2 Top side cover with knurled screws 1 X 110 RS232 SD Card X 107 X 108 USB 2 0 X 105 X 106...

Страница 76: ...nal interfaces Optional ext interfaces and onboard components Onboard controller Complex function PWR LED Power Button RSQ LED System EPROM SPI Flash RESCUE BIOS I 2 C SPI Gold CAP RTC Ultra low power...

Страница 77: ...Cover retaining bracket on the front side 2 LED indicators circuit 3 1x Mini PCIe socket for PCIe Mini card please observe the note below 4 PCI x8 socket not used in this configuration 5 Screws that s...

Страница 78: ...elow 1 Power on the board 2 Wait until the first characters appear on the screen POST messages or splash screen 3 Press the DEL key 4 If the uEFI BIOS is password protected a request for password will...

Страница 79: ...p menus The currently active menu and the currently active uEFI BIOS Setup item are highlighted in white Each Setup menu provides two main frames The left frame displays all available functions Config...

Страница 80: ...otal Memory and Memory Frequency PCH Information Read only field Displays PCH information Name PCH SKU Stepping and Hsio Revision Displays SPI Clock Information Read ID Status Clock Frequency Write an...

Страница 81: ...KBox C 102 User Guide Rev 1 0 www kontron com 81 Sub Screen Description System Date Sets the system date Week Day mm dd yyyy System Time Sets the system time hh mm ss...

Страница 82: ...additional information Table 8 Advanced Setup Menu Sub Screens and Functions Sub Screen Function Second level Sub Screen Description CPU Configuration Read only field Displays CPU Information Type ID...

Страница 83: ...C9 C8 C7S C7 C6 C3 C2 C0 C1 Thermal Monitor Enable disable thermal monitor Enabled Disabled GT Power management Control RC6 Render standby Check to enable render standby support Enabled Disabled Maxi...

Страница 84: ...R for Intel Mobile Processors is 119 127 C 119 C 111 C 103 C 100 C 95 C 87 C 79 C 71 C 63 C 55 C 47 C 39 C 31 C 23 C 15 C Passive Trip Point Controls temperature of ACPI Passive Trip Point at which OS...

Страница 85: ...orsement Hierarchy Endorsement Hierarchy Enabled Disabled TPM2 0 UEFI Spec Version Selects TCG2 Spec Version support TCG_1_2 is compatible mode for Win8 Win10 and TCG_2 supports TCG2 protocol event fo...

Страница 86: ...n be set to eight different fixed values between 1 second and 30 minutes Reset Button Behavior Selects reset button behavior Chipset Reset Power cycle I2C Speed Selects internal I2C bus speed between...

Страница 87: ...l Fan An external fan can be connected to baseboard The external fan s control lines are routed via the COMe connector 5 0V Standby Read only field Displays standby voltage Batt Volt at COMe Pin Read...

Страница 88: ...nabled Disabled SIO Configuration Serial Port 2 Use This Device Enables or disables the use of this logical device Enabled Disabled Logical Device Settings Current Read only field IO 3F8h IRQ 4 Logica...

Страница 89: ...60 192 224 248 Bus Clocks VGA Palette Snoop Enables or disables VGA palette register snooping Enabled Disabled PERR Generation Enables or disables PCI device to generate PERR Enabled Disabled SERR Gen...

Страница 90: ...r PCI devices Controls the OpROM execution policy for devices other than Network Storage or Video Do not launch UEFI Legacy Additional Information CSM Compatibility Support Module CSM configuration is...

Страница 91: ...upport Note Enable for USB keyboard legacy support for non USB aware OS s Enabled Disabled USB Transfer Time out Displays timeout value for control bulk and interrupt transfers 1 sec 5 sec 10 sec 20 s...

Страница 92: ...functions and describes the content Default settings are in bold Table 9 Chipset Set System Agent Configuration Sub Screens and Functions Function Second level Sub Screen Description SA PCIe Code Ver...

Страница 93: ...er Mode Used for SFF only Enabled Disabled VDD Enable Enables or disables VDD forcing in BIOS Enabled Disabled HDCP Support HDCP provisioning BIOS support Enabled Disabled Algorithm HDCP re encryption...

Страница 94: ...d HDMI DisplayPort configuration with external connectors DisplayPort Only DP with HDMI DVI HDMI DVI EFP3 LSPCON HDMI2 0 feature Level shifter protocol converter Enabled Disabled Mode Persistence Mode...

Страница 95: ...g Enabled Disabled Memory Configuration Read only field Memory RC version Memory frequency Memory timings tCL tRCD tRP tRAS Channel 0 slot 0 Size Channel 0 slot 1 Channel 1 slot 0 and Channel 1 slot 1...

Страница 96: ...xpress Clock Gating PCI Express clock gating for each root port Enabled Disabled Legacy IO Low Latency Enables low latency of legacy I O as some systems require lower I O latency irrespective of power...

Страница 97: ...en3 Eq Phase3 method PCIe Gen3 Equalization phase 3 method Hardware Static Coeff Software Search UPTP Upstream Port Transmitter Preset 5 DPTP Downstream Port Transmitter Preset 7 ACS Access Control Se...

Страница 98: ...IniPCIe J17 or J18 LTR PCH PCIE latency reporting Enabled Disabled Snoop latency Override Snoop latency override or Non Snoop Override for PCH PCIE Disabled to disable override Manual to manually ente...

Страница 99: ...abled Aggressive LPM Support Enable PCH to aggressively enter link power state Enabled Disabled SATA Controller Speed Displays the maximum support supported by SATA controller Default Gen1 Gen2 Gen3 S...

Страница 100: ...abled DITO Value Read only field 625 DM Value Read only field 15 USB Configuration XHCI Disable Compliance Mode Option to disable compliance mode Default is false and compliance mode is not disabled T...

Страница 101: ...ownership of the I O buffer between Intel HD audio link and I2S port for bilingual codecs HD Audio Link HD Audio Link I2S Port I2S Port I O Buffer Voltage Select Selects the voltage operation mode of...

Страница 102: ...sable this USB physical connector physical port Once disabled any USB devices plugged into the connector will not be detected by BIOS or OS Enabled Disabled Serial IRQ Mode Configure serial IRQ mode Q...

Страница 103: ...g setup If only the user s password is set then the password is a power on password and must be entered to boot or enter setup Within the setup menu the user has administrator rights Password length r...

Страница 104: ...Off Quiet Boot Enables or disables Quiet Boot Enabled Disabled Fast Boot Enables or disables boot with initialization of a minimal set of devices required to launch active boot option This has no eff...

Страница 105: ...Disk3 Boot Option 5 UEFI Hard Disk4 Boot Option 6 UEFI Hard Disk5 Boot Option 7 UEFI AP UEFI Built in EFI Shell Boot Option 8 UEFI CD DVD Boot Option 9 UEFI USB Hard Disk Boot Option 10 UEFI USB CD D...

Страница 106: ...xits system after saving the changes Discard Changes and Exit Exits system setup without saving any changes Save Changes and Reset Reset system after saving changes Discard Changes and Reset Resets sy...

Страница 107: ...http sourceforge net projects efi shell files documents Please note that not all shell commands described in the EFI Shell Command Manual are provided by the Kontron uEFI BIOS 15 1 uEFI Shell Introduc...

Страница 108: ...t and react by reset The uEFI Shell commands are not case sensitive Each uEFI Shell command is provided with a detailed online help that can be invoked by entering cmd space in the command line To dis...

Страница 109: ...named bootme nsh located in the root of the first detected disc drive fs0 fs0 bootme nsh 15 2 3 3 Enable Watchdog The uEFI Shell provides environment variables used to control the execution flow The f...

Страница 110: ...d myramdisk kbootscript p boot nsh 5 Reset the board to execute the newly installed script using the reset uEFI Shell command myramdisk reset 6 If a script is already installed it can be edited using...

Страница 111: ...RESCUE Button and RSQ LED The uEFI BIOS code and settings are stored in the SPI boot flashes Changes made to the uEFI BIOS settings are available only in the currently selected SPI boot flash Thus swi...

Страница 112: ...ED RSQ Rescue LED THERM Thermal LED DRIVE HDD SSD status LED SD SD Card status LED WD Watchdog status LED GP1 GP4 General purpose LEDs Interfaces front side accessible 3x Ethernet 10 100 1000 Mbit s 2...

Страница 113: ...e x1 4x PCI x4 2x full size Mini PCIe x1 2x PCIe x4 or 1x PCI 32 bit and 1x PCIe x4 via corresponding riser card power consumption less than 15W is allowed 2x full size Mini PCIe x1 1x PCIe x4 via cor...

Страница 114: ...tions of the KBox C 102 16 1 1 Mechanical Specifications of the KBox C 102 4 Figure 73 Dimensions right side KBox C 102 4 Figure 74 Dimensions front side with key holes KBox C 102 4 Figure 75 Dimensio...

Страница 115: ...with Fan Tray Option Figure 77 Dimensions right side KBox C 102 4 with fan tray option Figure 78 Dimensions front side with key holes KBox C 102 4 with fan tray option Figure 79 Dimensions detail key...

Страница 116: ...ounting brackets 290 mm 11 42 with mounting brackets 324 mm 12 756 Width 195 mm 6 10 195 mm 6 10 Depth with mounting brackets 210 mm 8 26 with mounting brackets 210 mm 8 26 Weight without packaging wi...

Страница 117: ...16 1 3 Mechanical Specifications of the KBox C 102 2 Figure 81 Dimensions right side KBox C 102 2 Figure 82 Dimensions front side with key holes KBox C 102 2 Figure 83 Dimensions detail key hole KBox...

Страница 118: ...with Fan Tray Option Figure 85 Dimensions right side KBox C 102 2 with fan tray option Figure 86 Dimensions front side with key holes KBox C 102 2 with fan tray option Figure 87 Dimensions detail key...

Страница 119: ...unting brackets 290 mm 11 42 with mounting brackets 324 mm 12 756 Width 155 mm 6 10 155 mm 6 10 Depth with mounting brackets 210 mm 8 26 with mounting brackets 210 mm 8 26 Weight without packaging wit...

Страница 120: ...16 1 5 Mechanical Specifications of the KBox C 102 1 Figure 89 Dimensions right side KBox C 102 1 Figure 90 Dimensions front side with key holes KBox C 102 1 Figure 91 Dimensions detail key hole KBox...

Страница 121: ...with Fan Tray Option Figure 93 Dimensions right side KBox C 102 1 with fan tray option Figure 94 Dimensions front side with key holes KBox C 102 1 with fan tray option Figure 95 Dimensions detail key...

Страница 122: ...ounting brackets 290 mm 11 42 with mounting brackets 324 mm 12 756 Width 130 mm 5 12 130 mm 5 12 Depth with mounting brackets 210 mm 8 26 with mounting brackets 210 mm 8 26 Weight without packaging wi...

Страница 123: ...6 1 7 Mechanical Specifications of the KBox C 102 0 Figure 97 Dimensions right side KBox C 102 0 Figure 98 Dimensions front side with key holes KBox C 102 0 Figure 99 Dimensions detail key hole KBox C...

Страница 124: ...102 0 Standard Version Height with mounting brackets 290 mm 11 42 Width 117 mm 4 61 Depth with mounting brackets 210 mm 8 26 Weight without packaging without expansions Approx 3 8 kg 8 37 lbs Chassis...

Страница 125: ...122 F Storage Transit Temperature 40 C 75 C 40 F 185 F Relative Humidity Operating 93 40 C non condensing acc to IEC 60068 2 78 Max Operation Altitude 2 000 m 6 560 ft Max Storage Transit Altitude 10...

Страница 126: ...E Information technology equipment Safety Part 1 General requirements EN 61010 1 U S A CANADA Conform UL STD 60950 1 Conform UL STD 508 Certified to CAN CSA C22 2 No 60950 1 UL 60950 1 Tested accordin...

Страница 127: ...ter 0 CS 03 Reserved 04 Reserved 05 RSTAT Reset Status Register CS 06 BICFG Board Interrupt Configuration CS 07 Reserved 08 BIDH Board ID Register High Byte ID 09 BREV Board and PLD Revision Register...

Страница 128: ...oftware Clearing is done by reset events P and S BFSS 1 0 Boot Flash Selections Status This bit field indicates which Flash device is currently in use or referenced and derived from rescue logic block...

Страница 129: ...t generated by CPLD logic 1 SYS_RESET generated by CPLD logic MWDTS Module Watchdog Trigger Status This bit if set reports COMe module caused reset by watchdog signal line WDT 0 System reset not gener...

Страница 130: ...uests as decoded as follows Table 30 Power Management Interrupt Configuration PMICF 1 PMICF 0 Interrupt request line 0 0 Disabled Default 0 1 LPT_ACK of Super I O 1 0 IRQ10 1 1 IRQ11 Recommended CICF...

Страница 131: ...Board ID Table 33 Board ID Register High Byte BIDH 0x108 Board ID Register High Byte BIDH Bit 7 6 5 4 3 2 1 0 Name BIDH 7 0 Access R Reset P EF 17 2 6 Board and PLD Revision Register Table 34 Board a...

Страница 132: ...aded mode dual stage WEN WTR Watchdog timer enable trigger This bit is used to enable and trigger the Watchdog timer 0 Watchdog timer not enabled Prior to the Watchdog being enabled this bit acts as t...

Страница 133: ...defining the onboard configuration for the front panel General Purpose LEDs Table 37 LED Configuration Register LCFG 0x110 LED Configuration Register LCFG Bit 7 6 5 4 3 2 1 0 Name LCON Access R W Rese...

Страница 134: ...status of a certain LED can be get by writing a get LED command including LED number color bits are ignored followed by a simple read LCMD 3 0 LED command This bit field is used to get and set a cert...

Страница 135: ...us This status bit indicates if fan is working correctly by analysis of fan tacho input signal FAN_TACHO This analysis is only done if FDIAG is set and the fan is activated indicated by FPWM is set to...

Страница 136: ...tor 18 1 2 X102 as ETH 1 and X103 as ETH 2 Ethernet Connectors Table 42 X102 X103 Ethernet Connectors Speed Mbps LINK ACT LINK ACTIVE 10 off on orange on blinking 100 green on orange on blinking 1000...

Страница 137: ...1 4 X107 X108 USB 2 0 Port Table 44 X107 X108 USB 2 0 Port Pin Signal Name 4 pin USB Connector Typ A Version 2 0 1 VCC 2 Data 3 Data 4 GND 18 1 5 X109 DisplayPort Table 45 X109 DisplayPort Pin Signal...

Страница 138: ...RS232 Table 46 X110 Serial Interface COM 1 RS232 Pin Signal Name 9 pin D SUB Connector male 1 DCD Data Carrier Detect 2 RXD Receive Data 3 TXD Transmit Data 4 DTR Data Terminal Ready 5 GND Signal Grou...

Страница 139: ...erfaces via Adapter Modules 18 2 1 X 201 LDT3 Table 47 X201 LDT3 18 2 2 X 202 DP 2 DisplayPort For Pin assignment refer to 18 1 5 Pin Signal Name LDT3 RJ45 female 1 TRD1 2 TRD1 3 TRD2 4 TRD3 5 TRD3 6...

Страница 140: ...abled 18 2 3 1 Serial Port RS232 RS422 configured as RS232 Table 48 Serial Port RS232 RS422 configured as RS232 Pin Signal Name 9 pin D SUB Connector male 1 DCD Data Carrier Detect 2 RXD Receive Data...

Страница 141: ...and 2 respectively pin 7 and 8 in order to enable the onboard termination resistor 120 Table 50 CAN Bus Port Pin Signal Name 9 pin D SUB Connector male 1 TERM L 2 CAN_L CAN_L bus line dominant low 3...

Страница 142: ...ly IOL IPMI Over LAN IOT Internet of Things IPMI Intelligent Platform Management Interface KCS Keyboard Controller Style KVM Keyboard Video Mouse MEI Management Engine Interface NCSI Network Communica...

Страница 143: ...KBox C 102 User Guide Rev 1 0 www kontron com 143...

Страница 144: ...dded technologies Kontron provides secure and innovative applications for a variety of industries As a result customers benefit from accelerated time to market reduced total cost of ownership product...

Отзывы: