AKD EtherCAT | 5 Appendix
5.3.2 Object 1001h: Error register (DS301)
This object is an error register for the device. The device can map internal errors into this
byte. It is a part of an Emergency object.
Index
1001h
Name
Error register
Object code
VAR
Data type
UNSIGNED8
Category
mandatory
Access
R/O
PDO mapping
not possible
Value range
UNSIGNED8
Default value
no
Error reasons to be signaled:If a bit is set to 1 the specified error has occurred. The generic
error is signaled at any error situation.
Bit Description
Bit Description
0 generic error
4 communication error (overrun, error state)
1 current
5 device profile specific
2 voltage
6 reserved (always 0)
3 temperature
7 manufacturer specific