TP-6461 1/08
28
Section 2 Controller Troubleshooting
2.6
Common Alarms
Any of the functions listed in Figure 2-8 can be assigned
to Common Alarms 1 and 2. Common alarms 1 and 2
can then be assigned to output functions which activate
when any of the conditions assigned to the common
alarm are present. Common Alarms 1 and 2 can also be
set to sound the alarm horn on the optional Alarm
Module.
If the common alarm is activated, the specific condition
that triggered the alarm will be shown on the ATS
controller display screen. Check the display to identify
the problem and then refer to the troubleshooting tables
in Sections 2.8 and 3.2.
Use the View Common Alarms screen to identify which
functions have been assigned to each common alarm.
See
the
Operation
and
Installation
Manual
for
instructions to check the view screens and to change the
settings, if necessary.
Selected functions as noted in Figure 2-8 are grouped
into the Critical Service Required and Non-Critical
Service Required functions.
The Critical Service
Required and Non-Critical Service Required functions
can be assigned to activate the alarm horn on the
optional Alarm Module. If any of the conditions included
in the Critical Service Required or Non-Critical Service
Required function occurs, the alarm horn will sound.
The message on the ATS display will identify which
condition (for example, Fail to Acquire Standby)
triggered the alarm and caused the horn to sound.
Functions that can be Assigned to Common Alarms
Aux Switch Fault *
Src E Over Freq
Aux Switch Open *
Src E Over Voltage
Battery Backup Low *
Src E Rotation Err *
Contactor in Off
Src E Under Freq
Contactor in Pref
Src E Under Voltage
Contactor in Src E
Src E Voltage Unbal
Contactor in Src N
Src N Loss of Phase
Contactor in Stby
Src N Over Freq
Exerciser Active
Src N Over Voltage
Fail to Acquire Pref *
Src N Rotation Err *
Fail to Acquire Stby *
Src N Under Freq
Fail to Transfer *
Src N Under Voltage
IPM Synching
Src N Voltage Unbal
Load Bank Control
Stby Src Available
Load Control Active
System Ready
Low Battery *
[
Test Mode Active
Non-Emergency Trans
Critical Service Required
Not in Auto
Man Transfer Waiting
Peak Shave Active
[
Module Lost Comm *
Pref Src Available
Non-Critical Service Req
Remote Common Alarm *
Source E Available
Remote Monitor In #1--4
Source N Available
Src E Loss of Phase
Modbus-Controlled RDO
#1--4
* Assigned to Critical Service Required
[
Assigned to Non-Critical Service Required
Figure 2-8
Common Alarm Functions
Содержание KGP
Страница 2: ......
Страница 6: ...TP 6461 1 08 6 Notes ...
Страница 10: ...TP 6461 1 08 10 Safety Precautions and Instructions Notes ...
Страница 22: ...TP 6461 1 08 22 Section 1 Scheduled Maintenance Notes ...
Страница 36: ...TP 6461 1 08 36 Section 2 Controller Troubleshooting Notes ...
Страница 54: ...TP 6461 1 08 54 Section 3 Transfer Switch Troubleshooting Notes ...
Страница 78: ...TP 6461 1 08 78 Section 4 Controller Test and Replacement Notes ...
Страница 86: ...TP 6461 1 08 86 Section 5 Component Replacement Model KGS KGP Notes ...
Страница 100: ...TP 6461 1 08 100 Section 6 Component Replacement Model KSS Switches Notes ...
Страница 125: ......