TP-6461 1/08
107
Section 7 Component Replacement, Model KSP
3. Remove two M4 bolts that secure the trip coil. See
Figure 7-23.
6226
1. Trip coil M4 bolts (2)
2. Trip shaft M4 bolt (and ring, not visible in this view)
3. Trip lever
1
2
3
Figure 7-23
Trip Coil and Trip Shaft Bolts
Spring-loaded parts.
Can cause severe personal injury
or property damage.
Wear
protective
goggles
when
servicing spring-loaded parts. Hold
parts securely during disassembly.
WARNING
4. The trip shaft is spring-loaded.
Hold the shaft
securely while removing the trip shaft bolt. See
Figure 7-24. Remove the M4 bolt with ring, trip
shaft, spring, and L-shaped bracket.
See
Figure 7-25. Keep the parts for reassembly later.
5. Loosen three bolts shown in Figure 7-26, remove
the side plate, and replace the trip coil.
See
Figure 7-26.
6226
1
1. Trip shaft
2. M4 bolt
2
Figure 7-24
Trip Shaft Location
6226
Figure 7-25
Trip Shaft Parts
6226
1. Bolts (3)
1
Figure 7-26
Side Plate Bolts
Содержание KGP
Страница 2: ......
Страница 6: ...TP 6461 1 08 6 Notes ...
Страница 10: ...TP 6461 1 08 10 Safety Precautions and Instructions Notes ...
Страница 22: ...TP 6461 1 08 22 Section 1 Scheduled Maintenance Notes ...
Страница 36: ...TP 6461 1 08 36 Section 2 Controller Troubleshooting Notes ...
Страница 54: ...TP 6461 1 08 54 Section 3 Transfer Switch Troubleshooting Notes ...
Страница 78: ...TP 6461 1 08 78 Section 4 Controller Test and Replacement Notes ...
Страница 86: ...TP 6461 1 08 86 Section 5 Component Replacement Model KGS KGP Notes ...
Страница 100: ...TP 6461 1 08 100 Section 6 Component Replacement Model KSS Switches Notes ...
Страница 125: ......