Section 2 Controller Troubleshooting
Event Description
The Controller Has Detected the Following Condition
Inhibit Transfer
Remote input assigned to inhibit transfer function is active (contact closed). Prevents transfer for
maintenance or service.
Remote Test
External signal (contact closure) connected to a programmable input assigned to remote test. Signals the
transfer switch to start a test sequence.
Low Battery Voltage
External battery (connected to the EBSM) voltage is low.
Remote Common Alarm
One or more conditions assigned to the common alram is active.
Bypass Contactor Dis
Bypass/Isolation switches only.
3 Src System Disable
A 3-Source System Disable input signal is active.
Over Frequency
Source frequency is above the over frequency dropout setting.
Under Frequency
Source frequency is below the under frequency dropout setting.
Phase Loss
One or more phases not detected.
Phase Rotation Error
Source ABC or BAC rotation does not match system setting.
Over Voltage L1--L2
Source voltage across L1 and L2 is above the over voltage dropout setting.
Over Voltage L2--L3
Source voltage across L2 and L3 is above the over voltage dropout setting.
Over Voltage L3--L1
Source voltage across L3 and L1 is above the over voltage dropout setting.
Under Voltage L1--L2
Source voltage across L1 and L2 is below the undervoltage dropout setting.
Under Voltage L2--L3
Source voltage across L2 and L3 is below the undervoltage dropout setting.
Under Voltage L3--L1
Source voltage across L3 and L1 is below the undervoltage dropout setting.
Voltage Imbalance
Source voltage imbalance detected.
Save History To File
Event history saved to a file.
Auto Loaded Test End
The auto load test sequence timer has expired, ending the test sequence.
Test Loaded Changed
The remote test loaded/unloaded setting was changed.
Pref Source Changed
The preferred source selection has been changed (optional accessory).
Reload Dflt Params
The system has been reset to the factory default settings (see Reset Data screen)
MODBUS Peak Shave
A peak shave command has been received through Monitor III or other Modbus application.
MODBUS Forced to OFF
A Transfer to OFF command has been received through Monitor III or other Modbus application.
MODBUS System Test
A Test command has been received through Monitor III or other Modbus application.
Battery Control Out
Battery control command turns off the battery 20 seconds after power is lost to preserve the controller’s
battery.
USB Connected
A device has been connected to the controller’s USB port.
USB Disconnected
A device has been disconnected from the controller’s USB port.
Figure 2-2
Event History Messages
Содержание KGP
Страница 2: ......
Страница 6: ...TP 6461 1 08 6 Notes ...
Страница 10: ...TP 6461 1 08 10 Safety Precautions and Instructions Notes ...
Страница 22: ...TP 6461 1 08 22 Section 1 Scheduled Maintenance Notes ...
Страница 36: ...TP 6461 1 08 36 Section 2 Controller Troubleshooting Notes ...
Страница 54: ...TP 6461 1 08 54 Section 3 Transfer Switch Troubleshooting Notes ...
Страница 78: ...TP 6461 1 08 78 Section 4 Controller Test and Replacement Notes ...
Страница 86: ...TP 6461 1 08 86 Section 5 Component Replacement Model KGS KGP Notes ...
Страница 100: ...TP 6461 1 08 100 Section 6 Component Replacement Model KSS Switches Notes ...
Страница 125: ......