TP-6461 1/08
38
Section 3 Transfer Switch Troubleshooting
Problem
See
Section
Check
Possible Cause
Generator set engine runs when it
should not
ATS does not recognize the
Normal source
Check connections.
Check voltage and frequency settings,
phase rotation, calibration.
Check for open switches or circuit
breakers.
—
2.4
ATS not in the expected position
Check the ATS position LEDs.
Check the position of the preferred
source selector switch, if equipped.
4.1
Exerciser is running
Check the controller display for
Exerciser Active message. Press the
END button to end an exercise run, if
necessary.
ATS O/I/M
Test sequence is running
Check the controller display for
indication that a test sequence is
active. Press the END TEST button to
end a test sequence, if necessary.
ATS O/I/M
Engine cooldown time delay
operating
Check for Engine Cooldown message
on the controller display. Press End
Delay button to end the cooldown
2.5
ATS O/I/M
Delay button to end the cooldown
delay, if necessary. Check the ATS
controller engine cooldown time delay
setting.
Check generator set controller engine
cooldown setting, if applicable.
Generator
O/M
Engine start connection closed
Check wiring and connections.
ATS O/I/M
W/D
Check that the 40-pin ribbon cable
connector between the logic and power
boards on the ATS controller is
connected.
4.2
Figure 4-5
Test the engine start contact operation.
4.7
Generator set master switch not in
AUTO
Move the generator set master switch
to the AUTO position. Wait for the
generator set engine cooldown delay, if
necessary.
Generator
set
manuals
Other generator set problem
Disconnect the engine start leads from
the ATS. If the engine continues to run,
troubleshoot the generator set.
Exerciser does not start generator
set
Exerciser not set
Use View Exercise Setup screen to
check exerciser settings.
ATS O/I/M
Check that exercise run duration
is not set to zero
Use View Exercise Setup screen to
check exerciser settings.
ATS O/I/M
Loose or open engine start
connection
Check wiring and connections.
ATS O/I/M
Engine start problem
Test engine start operation. Also see
“Generator set engine does not start,”
in this table.
4.7
O/I/M= Operation and Installation Manual; O/M = Operation Manual; TOC = Table of Contents, this manual;
W/D = Wiring Diagrams
Содержание KGP
Страница 2: ......
Страница 6: ...TP 6461 1 08 6 Notes ...
Страница 10: ...TP 6461 1 08 10 Safety Precautions and Instructions Notes ...
Страница 22: ...TP 6461 1 08 22 Section 1 Scheduled Maintenance Notes ...
Страница 36: ...TP 6461 1 08 36 Section 2 Controller Troubleshooting Notes ...
Страница 54: ...TP 6461 1 08 54 Section 3 Transfer Switch Troubleshooting Notes ...
Страница 78: ...TP 6461 1 08 78 Section 4 Controller Test and Replacement Notes ...
Страница 86: ...TP 6461 1 08 86 Section 5 Component Replacement Model KGS KGP Notes ...
Страница 100: ...TP 6461 1 08 100 Section 6 Component Replacement Model KSS Switches Notes ...
Страница 125: ......