TP-6461 1/08
102
Section 7 Component Replacement, Model KSP
3. Remove the auxiliary switches. See Figure 7-3.
1
6226
1. Auxiliary switches
Figure 7-3
Auxiliary Switches
4. Loosen four bolts and separate the mechanical unit
from the current-carrying unit.
See Figure 7-4,
Figure 7-5, and Figure 7-6.
Note:
The current-carrying unit on 400-models is
made up of sections that will separate when
disassembled.
1
6226
1. Loosen four M5 bolts
Figure 7-4
Separating Units, 100 and 200 Amp
6226
1. Loosen four M6 bolts
1
Figure 7-5
Separating Units, 400 Amp
6226
Figure 7-6
Mechanical Unit
7.2.2
Reassembly, 100--400 Amps
Reassemble
the
mechanical
unit
and
the
current-carrying unit.
1. Assemble the current-carrying unit and the
mechanical unit. Make sure that the shaft from the
mechanical unit goes through both main shaft
levers. See Figure 7-7.
On 400-amp units, the current-carrying unit is
made up of separate sections. Make sure that the
sections
are
flush
across
the
front
when
reassembling.
6226
1. Openings for shaft from coil
2. Main shaft levers
2
1
Figure 7-7
Current-Carrying Unit
Содержание KGP
Страница 2: ......
Страница 6: ...TP 6461 1 08 6 Notes ...
Страница 10: ...TP 6461 1 08 10 Safety Precautions and Instructions Notes ...
Страница 22: ...TP 6461 1 08 22 Section 1 Scheduled Maintenance Notes ...
Страница 36: ...TP 6461 1 08 36 Section 2 Controller Troubleshooting Notes ...
Страница 54: ...TP 6461 1 08 54 Section 3 Transfer Switch Troubleshooting Notes ...
Страница 78: ...TP 6461 1 08 78 Section 4 Controller Test and Replacement Notes ...
Страница 86: ...TP 6461 1 08 86 Section 5 Component Replacement Model KGS KGP Notes ...
Страница 100: ...TP 6461 1 08 100 Section 6 Component Replacement Model KSS Switches Notes ...
Страница 125: ......