TP-6461 1/08
72
Section 4 Controller Test and Replacement
4.12 File Transfer through the USB
Port
The Universal Serial Bus (USB) port on the main logic
board allows file transfer to and from a USB mass
storage device (removeable drive). Figure 4-17 shows
a typical device.
The removeable drive must
be
compatible with the USB 2.0 and USB Mass Storage
Device Class specifications.
The controller application code can be updated through
the USB port. Parameter settings, event history, and
other information files can be saved to the storage
device.
The controller recognizes the types of files shown in
Figure 4-18.
4.12.1 Configuration files
The configuration (.cfg) file contains the transfer switch
settings, including:
D
System setup
D
Source setup, including voltage and frequency
pickup and dropouts
D
Time delays
D
Inputs and outputs
D
Communications settings
D
Calibration factors
Configuration files from one transfer switch can be
saved to a mass storage device and then loaded onto
other transfer switches for quick setup of multiple
switches.
Serial numbers and descriptions entered
through
Monitor
III
software
(or
other
Modbus
application)
are
not
changed
by
downloading
configuration files to a transfer switch.
Check the settings and run a test sequence after loading
the configuration file to verify correct operation. Refer to
the
ATS Operation
and Installation
Manual for
instructions to view settings.
See Section 4.5 for
instructions to run a test.
Loading Settings when Controller is Replaced
If the controller needs to be replaced, the configuration
file from the old controller (if available) can be loaded
onto the new controller for quick setup.
Note:
Operation problems can be caused by incorrect
controller settings.
Do not load the old
configuration file onto the new controller unless
you are certain that all the settings in the file are
correct.
Note:
When replacing the ATS controller, record the
contactor and ATS serial numbers from the old
controller before removing it, or from the ATS
decals.
Serial numbers are not transferred through the
configuration file and cannot be entered through the
controller’s user interface.
Use Monitor III (or a
customer-provided Modbus driver designed for the
system) to enter the contactor and ATS serial numbers
after the new controller is installed. A distributor-level
password is required to enter serial numbers. Refer to
the Monitor III Operation Manual or the Modbus Protocol
Manual for instructions, if necessary. Do not attempt to
change the controller serial number.
Figure 4-17
Typical Mass Storage Device
File name
Description
Size (approx.)
Download to Control
Upload to USB
MPAC1500v###.bin
Controller application program
950 KB
X
MPAC1500_#######.cfg
Configuration (parameter settings)
3 KB
X
X
present
yymmdd
.his
Event history
varies
X
alarm_settings.alm
Common alarms
1 KB
X
MPAC1500_cal.cal
Calibration
1 KB
X
history_param.hstp
Internal use only
—
X
Param_back.bak
Internal use only
—
X
present
yymmdd
.raw
Internal use only
—
X
history_pback.hbak
Internal use only
—
X
Figure 4-18
Recognized File Types
Содержание KGP
Страница 2: ......
Страница 6: ...TP 6461 1 08 6 Notes ...
Страница 10: ...TP 6461 1 08 10 Safety Precautions and Instructions Notes ...
Страница 22: ...TP 6461 1 08 22 Section 1 Scheduled Maintenance Notes ...
Страница 36: ...TP 6461 1 08 36 Section 2 Controller Troubleshooting Notes ...
Страница 54: ...TP 6461 1 08 54 Section 3 Transfer Switch Troubleshooting Notes ...
Страница 78: ...TP 6461 1 08 78 Section 4 Controller Test and Replacement Notes ...
Страница 86: ...TP 6461 1 08 86 Section 5 Component Replacement Model KGS KGP Notes ...
Страница 100: ...TP 6461 1 08 100 Section 6 Component Replacement Model KSS Switches Notes ...
Страница 125: ......